Technical information
C-BUS
TM
LIGHTING CONTROL
+
DESIGN GUIDE
Ofces 1-4: Tandem wired 3-lamp uorescent luminaires (32W T8)
Lighting power density of 192W/225SF= .853 W/SF
Conf Room: Recessed 32W compact uorescent luminaires
120V phase angle dimming ballast per luminaire
Ofces 1-4: Multi-level control (0, 33%, 67%, 100%)
4-button keypad (all on, A on/off, B on/off, all off)
Occupancy sensor shutoff
Conf Room: Multi-Scene control with dimming control
Dynamic Labeling Technology keypad (4-buttons x 2 pages)
(6) preset scenes (all on, meeting, presentation, lecture, dining, all off)
Dim up/down table lights
Dim up/down room lights
Occupancy sensor shutoff
Equipment Selection by Space
Ofces 1-4: (1) C-Bus™ PIR 360° occupancy sensor per ofce
(1) 4-Button Neo
TM
Keypad per ofce
(2) 20A relay outputs per ofce
Conf Room: (2) C-Bus PIR 360° occupancy sensors
(1) DLTTMh Neo keypad
(4) 4A Phase angle dimmer outputs (1 per group)
C-Bus Input Unit Placement
Ofces 1-4: - Place keypad in wall box adjacent to entry
- Place occupancy sensor in ceiling over desk for best coverage
Conf Room: - Place DLT keypad in wall box adjacent to entry
- Place (2) occupancy sensors over table for best coverage
Space control
Offices 1-4
Tandem-Wired
3-Lamp
Luminaires
Neutral
Line
Ofce & Conference Room Design Project
Space Lighting
Design Project
151