Technical information
Catalog Number Description
SLSCDS2000 Ceiling Mounted Dual Technology Occupancy Sensor
SLSPP1277 Power Pack (required)
SLSSP24 Auxiliary Relay
Technical Information
Current Consumption 37mA Nominal
Supply Voltage 24Vdc
Isolated Relay 1A @ 24Vdc Resistive
Operating Temperature 32 - 122° F (0 - 50°C)
Max. Humidity 90% RH Non-condensing
Standards UL and cUL Listed FCC Part 15
Home and Ofce Use (Class B) Title 24 Certied
*For Diagram see technical section page 21
OCCUPANCY SENSORS
+
CEILING MOUNTED OCCUPANCY SENSORS
The Mounted Dual Technology Occupancy Sensor employs both passive infrared (PIR) and
ultrasonic technology to accurately detect occupancy and automatically turn on lighting.
To reduce the occurrence of false-on events, this sensor employs PIR technology to
detect major motion. Once lighting has been turned on, it employs highly sensitive PIR and
ultrasonic technology to detect minor motion and keep lighting on while the area remains
occupied. When the room or area is no longer occupied, the sensor turns off lighting after a
pre-set time delay.
The low prole sensor is ceiling mounted for greatest sensitivity to detect motion in large
areas with obstructions. With a 360 degree eld of view and up to 2000 square feet (185.8
sq. meters) of coverage area, the Ceiling Mounted Dual Technology Occupancy Sensor is
ideal for conference rooms, classrooms and large meeting rooms.
These ceiling mount sensors also incorporate an integral light level sensor to prevent lighting
from switching On when sufcient ambient light is present, such as is commonly found in
windowed areas.
Installation and conguration is simple. The sensor readily mounts to drop ceilings and
features front-located adjustments for setting sensitivity and time delay. The sensor also
features an isolated relay for use with building automation and HVAC systems.
Product Features
• Available in white, ivory, gray, light
almond and black with matching
wall switch cover plate
• Color matching multi-segmented
lens
• Selectable auto-on and manual-
on modes
• 120-277Vac 50/60Hz input
• 180° eld of view
• 1000 sq. ft. major motion and
300 sq. ft. minor motion coverage
area
• Light level sensor
• Walk-through mode
• Adjustable light level, time delay
and sensitivity
• Red LED motion indicator
• For use with electronic and
magnetic ballasts
• No neutral connection, minimum
load or power pack required
• UL and cUL Listed for United
States and Canada
• Test mode (15 second time delay)
• Five-year warranty
Ceiling Mounted Occupancy Sensor
Dual Technology
Dual Circuit Wall Switch
Occupancy Sensor