Technical information
Catalog Number Description
SLSWDS1500 Wall Mounted Occupancy Sensor Dual Technology
SLSPP1277 Power Pack (required)
SLSSP24 Auxiliary Relay
Technical Information
Current Consumption 37mA Nominal
Supply Voltage 24Vdc
Isolated Relay 1A @ 24Vdc Resistive
Operating Temperature 32 - 122° F (0 - 50°C)
Max. Humidity 90% RH Non-condensing
Standards UL and cUL Listed FCC Part 15
FCC Part 15, Home and Ofce Use (Class B)
Title 24 Certied
*For Diagram see technical section page 22
Wiring Color Table
Wire Color Functions
Black 0Vdc
Red +24Vdc
Green Isolated Contact (N.C.)
Yellow Isolated Contact Common
Orange Isolated Contact Common
Blue Control Output
*For Diagram see technical section page 22
*Control power must be provided by Schneider Electric Power Pack SLSPP1277 or approved equivalent. Confirm the
sensor is connected to the Class 2 side of the Power Pack. Refer to the Schneider Electric Power Pack SLSPP1277
Instruction Bulletin for additional information
Wall Mounted Occupancy Sensor
Dual Technology
C-BUS
TM
OCCUPANCY SENSORS
+
WALL MOUNTED OCCUPANCY SENSORS
Schneider Electric
®
Wall Mounted Dual Technology Occupancy Sensor employs both
passive infrared (PIR) and ultrasonic technology to accurately detect occupancy and
automatically turn on lighting.
To reduce the occurrence of false on events, this sensor employs PIR technology to
detect major motion. Once lighting has been turned on, it employs highly sensitive PIR
and ultrasonic technology to detect minor motion and keep lighting on while areas remain
occupied. When the room or area is no longer occupied, the sensor turns off lighting after a
pre-set time delay.
The low prole sensor is wall mounted for greatest sensitivity to motion in large areas with
obstructions. With a 110 degree eld of view and up to 2500 square feet of coverage area
when mounted at 8 ft. off the ground, the Wall Mounted Dual Technology Occupancy
Sensor is ideal for conference rooms, classrooms, bathrooms, and large ofce areas.
These wall mount sensors also incorporate an integral light level sensor to prevent lighting
from switching On when sufcient ambient light is present, such as is commonly found in
windowed areas.
Installation and conguration is simple. The sensor readily mounts to walls and drop ceilings
and features front located adjustments for setting sensitivity and time delay. The sensor also
features an isolated relay for use with building automation and HVAC systems.
Product Features
• 2500 sq. ft. coverage area @ 8 ft.
• 110 degree eld of view
• Light Level Sensing (from 0.5 to
250 foot-candles)
• Adjustable Time Delay
(pre-set time delays from 15
seconds to 30 minutes)
• Adjustable Sensitivity (from 60
to 100%)
• Isolated Relay
• Red and green LED motion
indicators
• Manual Bypass
• Front located adjustment access
cover
• UL
®
/cUL Listed
Wall Mounted Occupancy Sensor
Dual Technology
16