Technical information
Catalog Number Description
SLSPIP210 Basic Occupancy Sensor
SLSPIP211 Single Output Occupancy Sensor
SLSPIP212 Dual Output Occupancy Sensor
SLSPCW001 Optional Counterweight
Technical Information
Fixture Compatibility HID with constant wattage auto-transformer ballast
Dimming Method Relay-switched dual-section capacitor*
Switching Congurations Parallel (preferred) or series capacitors
Relay Current Rating 4 amperes RMS maximum
Maximum Fixture Wattage 1000 watts parallel mode/250 watts series mode
AC Line Voltage 208/240/277/347/480VAC
Power Consumption 3 watts maximum
Maximum Fiber Spacing 200 ft.
Between Nodes
Ambient Temperature Range 32O to 122O F (0O to 50O C) non-condensing
Observed Motion ON Time 0 to 15 minutes (user-adjustable)
Lamp Warm Up Interval 15 minutes
Wire Harness 4 conductor 18 AWG stranded copper wire
Wire Harness Length 36 inches (91.44 cm)
Dimensions 3.25 in. (L) x 3.25 in. (W) x 3.25 in.(H)
(including mounting nipple) [82.56 mm (L) x 82.56 mm (W) x 82.56 mm (H)]
Standards UL®: Listed 916 Energy Management Equipment cUL: Listed
*For Diagram see technical section page 22
Sensor and optional counterweight
mounted on luminaire
OCCUPANCY SENSORS
+
HIGH BAY OCCUPANCY SENSORS
Schneider Electric High Bay HID Basic, Single and Dual Output Occupancy Sensors
work with a single HID (high intensity discharge) luminaire to reduce the lamp wattage
by approximately 50% and then return the lamp wattage to 100% when occupancy is
detected in an aisle or room. Motion is detected using passive infrared (PIR) technology.
Basic HID Sensors are used in sensor-per-xture conguration, while single output
sensors include a connector to send and receive ber optic signals. Single output
sensors are commonly used in daisy chain congurations. Dual output sensors have two
connectors that send ber optic signals, and are commonly used in congurations that
interleave switch packs and sensors. All Sensors are compatible with single magnetic
HID luminaires.
Product Features
• Compatible with HID luminaires rated
between 208 and 480VAC/60Hz,
without adding taps or jumpers
• Up to 40’ mounting height
• User-adjustable 1 to 15 minute activity
timer
• User-adjustable range dial to
customize PIR sensitivity
• Available with interchangeable aisle
and area lenses
• Lamp always starts on high to provide
full rated HID lamp life, even after AC
power bumps or loss of ber optic
signals
• Includes a manual test switch for self
diagnostics that assist with installation
and debugging networks