Technical information
Catalog Number Description
SLC5500TPS 120Vac Power Supply
SLC5500HPS 277Vac Power Supply
Technical Information
Nominal Line Voltage Operates at 120 or 277Vac, ± 10%, with a frequency range from 50–60 Hz
Electrical Isolation 3.75 kV RMS from C-Bus to the line
Current Output 350 mA to the C-Bus network
Status Indicators Unit: Unit power
C-Bus: Network voltage level and
presence of system clock
Power Supplies per Network Up to ve power supplies on a single C-Bus network
C-Bus Connection (2) RJ-45 sockets for connection to the C-Bus network
Cable (1) 15.75 in. (400 mm) patch lead included
Dimensions 3.35 in. (H) x 2.84 in. (W) x 2.60 in. (D)
[85 mm (H) x 72 mm (W) x 66 mm (D)]
Mounting DIN rail, 4M wide
Weight 7 oz (200 g)
Operating Temp.: 32°F to 104°F (0°C to 40°C)
Environment RH: 95%, noncondensing
Storage Temp.: 14°F to 140°F (–10°C to 60°C)
Environment RH: 95%, noncondensing
Standards UL: Listed 916 Energy Management Equipment
CSA 22.2 Spec 205 Signal Equipment
FCC: Part 15.101, Class B Digital Device
EN61000-4-2 Immunity to ESD
*For Diagram see technical section page 99
C-BUS
TM
LIGHTING CONTROL
+
SYSTEM UNITS
The C-Bus
TM
Power Supply is specically designed to operate with the C-Bus network
as a power source for passive C-Bus devices.
The power supply mounts to a DIN rail and connects to the C-Bus network through
built-in RJ-45 connectors.
These devices are UL listed as Class 2 power supplies and are suitable for parallel
operation. Up to ve power supplies can be connected to a single C-Bus network.
Power Supply
Product Features
• Available in 120 and 277Vac models
• Regulating power supply compensates for
line voltage and frequency variations, so there
is constant output
• Sources up to 350 mA to the C-Bus network
• UL listed to operate in parallel with other
C-Bus power supplies, up to ve on a single
C-Bus network
• Incorporates short circuit and reverse polarity
protection
• Indicates the line voltage status with a Unit
LED
• Indicates the network status, including the
network power and the presence of the
C-Bus clock, with a C-Bus LED
• Standard built-in C-Bus network connectors:
(2) RJ-45
Distributed Intelligence
• Compatible with all C-Bus devices and
Powerlink
®
NF3000G3C controllers
• Easily congured by using the C-Bus Tool Kit
software
C-Bus
TM
Power Supply
62