Technical information

Technical Information
Nominal Voltage Requirements 15-36 volts @18 mA from the C-Bus network
Nominal 120Vac
Nominal Supply Voltage 16-27V AC/DC, +/- 10%, 50-60 Hz,
provided by an external power supply (included)
AC Input Impedance 100 kOhm @ 1 kHz
External Power Supply 24Vac @ 500 mA
Electrical Isolation 500 V RMS per input
Nominal 24Vdc Output Voltage 24Vdc @ 250 mA, ±10% General Input
Digital Sensor Input TTL, 5V from external source
Analog Sensor Inputs:
Voltage Ranges 0–1, 0–5, 0–10, 0–20Vdc
Input Current Ranges 0–20 mA DC, 4–20 mA DC
Resistance Ranges 0–500 ohm, 0–1000 ohm, 0–3000 ohm, 0–10000 ohm
Maximum Input Voltages -20 V to 60Vdc
Input Voltage Range Impedance At least 100 kOhm
Current Sense Impedance 249 ohm
Resistance Range Injection Current 500 μA
Basic Accuracy after Calibration 0.5% of full scale
Maximum Input Frequency 10 Hz
Broadcast Rates 2–1024 sec
Number of Units per Network 10
C-Bus Connections (2) RJ-45 connectors, CAT 5 UTP cable required
Cable 15.75 in. (400 mm) patch lead included
Terminals Accommodate 16–12 AWG cable (2 x 1.31 mm
2
or 1 x 3.31 mm
2
)
Status Indicators Unit/Comms: Unit power and data transmission
C-Bus: Power levels and presence of C-Bus clock
Dimensions 5.7 in. (L) x 3.4 in. (W) x 2.6 in.(H) [144 mm (L) x 85 mm (W) x 65 mm (H)]
Weight 7 oz (190 g)
Mounting DIN rail, 8M wide
Operating Environment 32°F to 113°F (0°C to 45°C) RH: 95%, noncondensing
Standards CSA 22.2 Spec 205 Signal Equipment
FCC: Part 15.101, Class B Digital
EN61000-4-2 Immunity to ESD
UL Listed 916 Energy Management Equipment
*For Diagram see technical section page 100
Catalog Number Description
SLCE5504TGI 4 Channel General Input Unit
C-BUS
TM
LIGHTING CONTROL
+
INPUT UNITS
The C-Bus
TM
Four-Channel General Input Units are DIN-rail mounted devices that
measure TTL digital and real-world analog quantities and generate messages about the
measurements to the C- Bus network. By acting as an interface with various external
sensors, the general input unit enables integration of the C-Bus network with a variety of
system types, such as those for HVAC and for power monitoring.
Conguration options include selectable input types, eight adjustable decision thresholds
per channel, denable actions, selectable ltering, broadcast rates, and a separate
hysteresis value per channel.
General Input Unit
Product Features
Measures TTL digital quantities including
voltage, current, or resistance from external
sensors such as light level, pressure, and
temperature
Four channels of input, each with an
adjustable hysteresis value, eight decision
thresholds, and a software-selectable input
value transformation in the form y = ax +b
Input channels are compatible with a range of
third-party sensors
Look-up table with interpolation
Capable of threshold switching or
broadcasting values onto the network
Control functions include load switching,
dimming, trigger applications, enable control
applications, and measurement applications
Measures input signals up to 10 Hz and has
an adjustable input-signal lter to reduce
susceptibility to impulse and noise
Supplies 250 mA to external sensors
LEDs indicate the status of the network
at the unit and the unit’s power and data
transmissions
Software-selectable network burden and
C-Bus system clock
Standard built-in C-Bus network connectors:
(2) RJ-45
Non-volatile memory stores operating status
for recovery from a power outage
Includes 120V/24V AC power pack
Distributed Intelligence
Compatible with all C-Bus devices and the
Powerlink
®
NF3000G3C controller
• Easily congured with the C-Bus Toolkit
Software
C-Bus
TM
General Input Unit