Technical information

Catalog Number Description
SLC5102BCLEDL Two-Channel Bus Coupler
SLC5104BCL Four-Channel Bus Coupler
Technical Information
Nominal Voltage 15-36Vdc @ 18 mA, drawn from the
Requirements C-Bus network
Electrical Isolation None
Voltage Across Input External Switch Opens: 5Vdc
External Switch Closes: 0Vdc
Current–Switch Closed Less than 50 μA
Distance Between 2-Channel Coupler: Up to 1 ft (0.3 m) each
Switch and Bus Coupler 4-Channel Coupler: Up to 3 ft (1 m) each
LED Drive Output 2-Channel Coupler only: 2 mA @ 12 V
Maximum Input Voltages -20 to 60Vdc
Number of Units Use the C-Bus Calculator, a software utility, to determine
per Network the total network current load
C-Bus Connections Two-way removable screw-type terminals accommodating
24–16 AWG cable (0.2–1.31 mm
2
)
Channel Input Spring-loaded terminal block accommodating
Connections 24–12 AWG cable (0.2–3.31 mm
2
)
Status Indicators Channel (2 or 4)
Timers 1 sec–18 hr, 1 sec intervals
Dimensions 2.2 in. (L) x 1.9 in. (W) x 0.7 in. (H)) [55 mm (L) x 49 mm (W) x 18 mm (H)]
Weight 1.1 oz (32 g)
Operating Environment 32°F to 113°F (0°C to 45°C) RH: 95%, noncondensing
Standards UL: Listed 916 Energy Management Equipment
CSA 22.2 Spec 205 Signal Equipment
FCC: Part 15.101, Class B Digital,
EN61000-4-2 Immunity to ESD
*For Diagram see technical section page 100
C-BUS
TM
LIGHTING CONTROL
+
INPUT UNITS
The C-Bus
TM
Bus Couplers are non-isolated input devices that provide an interface
between dry-contact mechanical switches and a C-Bus network. The bus coupler
increases the versatility of the C-Bus network by facilitating remote access with any dry-
contact switch mechanism offered by Schneider Electric and other manufacturers.
A system’s exibility can be further enhanced by using the bus coupler with various other
switch types, including reed, pressure, or micro switches.
Available in two- and four-channel models, the bus coupler is small enough to be used in
restricted spaces. Conguration options include standard control functions such as ON/
OFF, toggle, dimmers, and timers.
Product Features
Provides two or four non-isolated inputs for
external voltage-free mechanical switches.
Two-channel units feature independent remote
LED outputs
• Control options include ON/OFF, toggle,
dimmer, or timer
Orange LED for each channel to indicate
operational status
Two-way removable terminal block for the
C-Bus connection
Terminal block allows connection of up to four
external switches (four-channel coupler) or two
external switches and two external LEDs (two-
channel coupler)
Small size for adaptation to restricted spaces
Non-volatile memory stores operating status
for recovery from a power outage
Receives data and power over a network, so
it does not require power packs or line voltage
connections
Distributed Intelligence
Compatible with all C-Bus devices and the
Schneider Electric Powerlink
®
NF3000G3C
controller
Easily congured by using Learn Mode or the
C-Bus Toolkit Software
Four-Channel Bus Coupler
C-Bus
TM
Bus Coupler
68