Catalog Number Description
SLCLE5504AUX 4 Channel Auxiliary Input Unit
Technical Information
Nominal Voltage Requirements 15-36Vdc @ 18 mA, drawn from the C-Bus network
Electrical Isolation C-Bus/Remote Input: 500 V RMS
Remote Input: 500 V RMS
Voltage Across Input External Switch Opens: 5Vdc External Switch Closes: 0Vdc
Current–Switch Closed 0.4 mA
Switch Resistance Up to 1000 ohm, including cable resistance (26.5 ohms per km
resistance for #18 copper wire coated DC current resistance)
Number of Units Use the C-Bus Calculator, a software utility,
per Network to determine the total network current load
C-Bus Connections (2) RJ-45 connectors, CAT 5 UTP cable required
Cable 15.75 in. (400 mm) patch lead included
Terminals Accommodate one 12 or two 14-22 AWG cables
(1 x 3.1 mm2) or 2 x 2.0-0.3 mm2)]
Status Indicators Channel: (4) orange LEDs to indicate the load status for each channel
Timers 1 sec–18 hr, 1 sec intervals
Dimensions 3.4 in. (L) x 2.8 in. (W) x 2.6 in. (H)) [85 mm (L) x 72 mm (W) x 65 mm (H)]
Weight 4.6 oz (130 g)
Mounting DIN rail, 4M wide
Operating Environment 32°F to 113°F (0°C to 45°C) RH: 95%, noncondensing
Standards UL: Listed 916 Energy Management Equipment
CSA 22.2 Spec 205 Signal Equipment
FCC: Part 15.101, Class B Digital Device
EN61000-4-2 Immunity to ESD
*For Diagram see technical section page 101
C-BUS
TM
LIGHTING CONTROL
+
INPUT UNITS
The C-Bus
TM
Four-Channel Auxiliary Inputs are isolated four-channel input units that
provide an interface between voltage-free mechanical switches and a C-Bus network.
An auxiliary unit increases the versatility of the C-Bus network by facilitating remote
access with any dry-contact switch mechanism offered by Schneider Electric or other
manufacturers.
DIN-rail mounted for quick installation, the auxiliary unit can be congured with standard
C-Bus control functions such as remote scene triggering, ON/OFF, toggle, dimmer, or
timer.
Product Features
Provides four isolated inputs for external
voltage-free mechanical switches
Control options include remote scene
triggering, ON/OFF, toggle, dimmer, or timer
operations
Orange LEDs indicate operational status, one
for each channel
Standard built-in C-Bus network connectors:
(2) RJ-45
Non-volatile memory stores operating status
for recovery from a power outage
Distributed Intelligence
Compatible with all C-Bus devices and the
Powerlink
®
NF3000G3C controller
Easily congured by using Learn Mode or the
C-Bus Toolkit Software
Four-Channel
Auxiliary Input Unit
C-Bus
TM
Four-Channel Auxiliary Input