Nominal Voltage Requirements 15-36Vdc @ 18 mA, drawn from the C-Bus network
Field of View 360°
PIR Rated Typically 800 sq ft (74 sq m) when sensor is
Detection Field mounted 8 ft (2.4 m) above oor
Light-Level inhibit Threshold 0.1 footcandle (1 lux) to full sunlight
Timer Delay 0 sec to 18 hr
Number of Units Use the C-Bus Calculator, a software utility, to
per Network determine the total network current load
C-Bus Connection Two removable terminal blocks, requires CAT 5 data cable
Status Indicators LED can be congured to turn on when movement is detected
Dimensions 4.1 in. (L) x 2.8 in. (W) [103 mm (L) x 72 mm (W)]
Weight 4.4 oz (125 g)
Mounting Surface: Ceiling
Ht: 8 ft (2.4 m) above oor
Max. Ht: 12 ft (3.7 m) above oor
Min. Ceiling Thickness: 0.4 - 0.75 in. (10 - 19.1 mm)
Operating Indoor only
Environment 32°F to 113°F (0°C to 45°C)
RH: 95%, noncondensing
Standards UL: Listed 916 Energy Management Equipment
CSA 22.2 Spec 205 Signal Equipment
FCC: Part 15.101, Class B Digital Device
EN61000-4-2 Immunity to ESD
*For Diagram see technical section page 101
Catalog Number Description
SLC5753L 360° PIR Occupancy Sensor
C-BUS
TM
LIGHTING CONTROL
+
SENSORS
Product Features
360° detection pattern, indoor use
Effective coverage area is more than 800 square
feet when unit is mounted 8 feet above the oor
Dual element detectors minimize false triggering
LEDs indicate movement detection and status
of the IR receiver, and the light-level sensor
Can control up to four scenes or group
addresses that can be individually scheduled
Adjustable light-level sensor with Sunrise/
Sunset and clock overrides
Attractive, low prole unit can be ush mounted
on ceiling or suspended from wall tiles where it
is unobtrusive, with a face diameter of only 2.8
inches
Non-volatile memory stores operating status for
recovery from a power outage
Receives data and power over a network.
No power packs or line voltage connections
required
Distributed Intelligence
Compatible with all C-Bus devices and the
Powerlink
®
NF3000G3C controller
Easily congured by using Learn Mode or the
C-Bus Toolkit Software
The C-Bus
TM
360° Indoor PIR Occupancy Sensor combines a passive infrared receiver
(PIR) for occupancy sensing and a light-level sensor into a small, highly versatile unit. The
multi-sensor’s 2.8 inch face diameter makes it unobtrusive and ideally suited for ush
mounting on the ceiling.
This sensor has a 360 degree eld of view with an effective coverage pattern of more
than 800 feet, so it is ideally suited for ofces, copier rooms, closets, and restrooms.
Multiple sensors can be connected to the same C-Bus network to provide larger
coverage patterns.
Conguration options include adjustable time delays for automatic shut-off following a
preset time period without detected motion and an adjustable light-level sensor that can
be set to automatically turn off lights when ambient light levels are sufcient or turn on
lights when ambient light levels are insufcient.