Technical information
Technical Information
Nominal Voltage Requirements 15-36Vdc @ 18 mA, drawn from the C-Bus network
Field of View 360°
PIR Rated Typically 800 sq ft (74 sq m) when sensor is
Detection Field mounted 8 ft (2.4 m) above oor
Light-Level inhibit Threshold 0.1 footcandle (1 lux) to full sunlight
Timer Delay 0 sec to 18 hr
Number of Units Use the C-Bus Calculator, a software utility, to
per Network determine the total network current load
C-Bus Connection Two removable terminal blocks, requires CAT 5 data cable
Status Indicators LED can be congured to turn on when movement is detected
Dimensions 4.1 in. (L) x 2.8 in. (W) [103 mm (L) x 72 mm (W)]
Weight 4.4 oz (125 g)
Mounting Surface: Ceiling
Ht: 8 ft (2.4 m) above oor
Max. Ht: 12 ft (3.7 m) above oor
Min. Ceiling Thickness: 0.4 - 0.75 in. (10 - 19.1 mm)
Operating Indoor only
Environment 32°F to 113°F (0°C to 45°C)
RH: 95%, noncondensing
Standards UL: Listed 916 Energy Management Equipment
CSA 22.2 Spec 205 Signal Equipment
FCC: Part 15.101, Class B Digital Device
EN61000-4-2 Immunity to ESD
*For Diagram see technical section page 101
Catalog Number Description
SLC5753L 360° PIR Occupancy Sensor
C-BUS
TM
LIGHTING CONTROL
+
SENSORS
Product Features
• 360° detection pattern, indoor use
• Effective coverage area is more than 800 square
feet when unit is mounted 8 feet above the oor
• Dual element detectors minimize false triggering
• LEDs indicate movement detection and status
of the IR receiver, and the light-level sensor
• Can control up to four scenes or group
addresses that can be individually scheduled
• Adjustable light-level sensor with Sunrise/
Sunset and clock overrides
• Attractive, low prole unit can be ush mounted
on ceiling or suspended from wall tiles where it
is unobtrusive, with a face diameter of only 2.8
inches
• Non-volatile memory stores operating status for
recovery from a power outage
• Receives data and power over a network.
No power packs or line voltage connections
required
Distributed Intelligence
• Compatible with all C-Bus devices and the
Powerlink
®
NF3000G3C controller
• Easily congured by using Learn Mode or the
C-Bus Toolkit Software
The C-Bus
TM
360° Indoor PIR Occupancy Sensor combines a passive infrared receiver
(PIR) for occupancy sensing and a light-level sensor into a small, highly versatile unit. The
multi-sensor’s 2.8 inch face diameter makes it unobtrusive and ideally suited for ush
mounting on the ceiling.
This sensor has a 360 degree eld of view with an effective coverage pattern of more
than 800 feet, so it is ideally suited for ofces, copier rooms, closets, and restrooms.
Multiple sensors can be connected to the same C-Bus network to provide larger
coverage patterns.
Conguration options include adjustable time delays for automatic shut-off following a
preset time period without detected motion and an adjustable light-level sensor that can
be set to automatically turn off lights when ambient light levels are sufcient or turn on
lights when ambient light levels are insufcient.
360° PIR Occupancy Sensor
C-Bus
TM
360° PIR Occupancy Sensor
71