C-Bus network supply voltage 15 to 36Vdc @ 32mA required for programming and operation
Maximum units per C-Bus network 50
C-Bus connections 2 wire, twisted pair
Warm up time 5 seconds
Load rating per relay channel 2A at 30Vdc maximum or
30Vac RMS suitable for resistive and inductive loads
Contact type Voltage free, SPDT (changeover)
Relay terminal connections C common, N/O normally open, N/C normally closed
Types of electrical connection Fixed load terminal for: 1 x 1.0mm² wire per tunnel (13AWG),
Fixed aux (C-Bus) connectors for: 2 x 1.5mm²
Dimensions (W x H x D) 8.66 x 3.15 x 1.50in. (220 x 80 x 38mm)
Weight 11.64oz (330g)
Mounting mode Surface: 4 mounting screw holes and keyhole mount
EMC environment Environment A
Operating ambient temperature 32 to 122°F (0 to 50°C)
Storage temperature 32 to 140°F (0 to 60°C)
Operating humidity 10 to 90% non condensing
Standards: CSA C22.2 No. 205 - Signal Equipment
UL916 - Energy Management Equipment, FCC Part
15 - Class B Digital Device for Home or Ofce Use
*For Diagram see technical section page 105
C-BUS
TM
LIGHTING CONTROL
+
OUTPUT UNITS
Catalog Number Description
SLC5108RELVP  C-Bus 8 Channel Low Voltage Relay
The C-Bus
TM
8 Channel Low Voltage Relay is used for switching loads such as irrigation
solenoids, and LV air conditioning dampers. The Relay may also be used for switching LV
pulse signal control loads into third party products.
The C-Bus 8 Channel Low Voltage Relay is a C-Bus output device that controls eight
low voltage relay channels. The unit is powered from the C-Bus network and requires
no other power source. The unit can be daisy chained or placed at the end of a C-Bus
network.
Product Features
Software-selectable C-Bus system clock
• Synchronize data communication on the
C-Bus network
• Switch Low Voltage Loads
• Control 3rd party products
• 2 Status Indicator Lights
Low Voltage Relay
C-Bus
TM
Low Voltage Relay