Datasheet

36
TAC Xenta 280
A compact, freely programmable controller which is LonMark
®
certified and
has fixed inputs and outputs. The controller is available in three different
versions:
TAC Xenta 281 (12 physical inputs/outputs)
TAC Xenta 282 (16 physical inputs/outputs)
TAC Xenta 283 (12 physical inputs/outputs)
The controllers can be easily programmed using the graphical programming
tool TAC Menta. The controllers can be used in a stand-alone system, where
the TAC Xenta OP can be used for displaying and operating the controller.
Controllers can alternatively be used in larger LonWorks
®
networks.
SPECIFICATIONS
Operating voltage . . . . . . . . . . . . . . . . . 24 V AC/DC ±20%, 50/60 Hz
Power consumption . . . . . . . . . . . . . . . . max. 5 W
Data backup in event of power failure . . 72 h RAM-Backup
Ambient Temperature
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . –20 °C to +50 °C
(4 °F to +122 °F)
Operation . . . . . . . . . . . . . . . . . . . . . . . 0 °C to +50 °C
(+32 °F to +122 °F)
Humidity . . . . . . . . . . . . . . . . . . . . . . . . max. 90% RH non-condensing
Dimensions incl. base . . . . . . . . . . . . . . 180 x 110 x 77mm
(7” x 4.3” x 3”)
Protocol . . . . . . . . . . . . . . . . . . . . . . . . . FTT-10, LonTalk
®
Transmission rate . . . . . . . . . . . . . . . . . . 78 kbits/s
External LonWorks
®
data points
Input variable . . . . . . . . . . . . . . . . . . . . . max. 15 SNVTs
Output variable . . . . . . . . . . . . . . . . . . . max. 30 SNVTs
Interfaces
Serial connection . . . . . . . . . . . . . . . . . . RS232, RJ45
Operator panel . . . . . . . . . . . . . . . . . . . . Modular jack, LonTalk
®
Protocol
DESCRIPTION
0-073-0030-0 TAC Xenta 281
0-073-0031-0 TAC Xenta 282
0-073-0032-0 TAC Xenta 283
ACCESSORIES
0-073-0901-0 Terminal part for all Xenta 280/300
0-073-0920-0 TAC Xenta: Programming Serial Kit
Programmable Controllers
Unit DI DO UI TI AO
TAC Xenta 281 2 3 4 3
TAC Xenta 282 2 4 4 2 4
TAC Xenta 283 2 6 4
FUNCTIONAL FEATURES
Optimized for maximum flex-
ibility in HVAC control with on
board inputs and outputs
Fully programmable using the
intuitive TAC Menta program-
ming tool
Intelligent start time calcula-
tion minimizing energy usage
Designed for use in open
systems and integration via
LonWorks
Available in a range of models
to secure cost-efficiency for
each application
Designed to work with TAC
Vista