Product manual

TAC Xenta 527-NPR, Product Manual 3 Commissioning the TAC Xenta 527-NPR
Schneider Electric Buildings AB, Mar 2010 17 (42)
04-00053-01-en
3 Commissioning the TAC Xenta 527-NPR
There are six basic steps to commissioning the Xenta 527-NPR. These
steps are described below.
1 Connect the Xenta 527-NPR to 24 VAC power.
Refer to the TAC Xenta 500/700/911/913, Installation Instruction
for instructions.
2 Connect a PC to the Xenta 527-NPR.
3 Attach a serial cable from the computers COM port to the RS-232
A port on the front of the Xenta 527-NPR, if you are going to use
the the NetPlus Router Configuration editor in I/NET,
or
attach a serial cable from the computer’s COM port to the RS-232
B port on the front of the Xenta 527-NPR, if you are going to use
the the EIndows Hyper Terminal.
Refer to the TAC Xenta 500/700/911/913, Product Manual for
complete instructions.
4 Set the Xenta 527-NPR’s communication parameters using Win-
dows Hyper Terminal or the NetPlus Router Configuration editor
in I/NET.
Before the Xenta 527-NPR can successfully communicate on the
Ethernet, you must first set its IP address and other basic parame-
ters. Refer to the TAC Xenta 500/700/911/913, Product Manual for
complete instructions.
5 Connect the Xenta 527-NPR to the Ethernet, if required.
Attach the Xenta 527-NPR to the network at the necessary location.
Refer to Chapter 4, “Connecting the TAC Xenta 527-NPR to Your
Network”, on page 19 for more information.
6 If necessary, load the Xenta 527-NPR’s software.
The Xenta 527-NPR is delivered from the factory with preloaded
software. If the need should arise to reload this software, you can
download it from Schneider Electric’s website. Before installing
downloaded software, review its release information to verify com-
patibility with your hardware.
7 Configure the Xenta 527-NPR to communicate with I/NET.
In order for the Xenta 527-NPR to communicate with I/NET
devices from across an Ethernet, you must first define basic com-