Datasheet
INSTALLATION MATERIAL/THORSMAN/MC1038INT/GB 75
Material and Product Properties
TET, TCF and TCG
Grade
Type designation
Colour
Weather
resistance
Temperature
resistance
Ageing in heat
Fire resistance
Chemical
resistance
Oil resistance
EPDM
TET
Grey
Weather and temperature
resistant. Can be used both
indoors and outdoors.
For continuous use between
-40°C and +100°C. (Cf.
natural rubber: Max.
+70°C). Somewhat higher
temperatures for short pe-
riods of time (+130°C for
approx. 1 hour).
After 168 hours at +70°C.
Property changes:
Hardness +2 ° Shore
(+3%)
Ultimate tensile strength
-9%
Elongation at break -17%
After 72 hours at +100°C.
Property changes:
Hardness +7 ° Shore
(+11%)
Ultimate tensile strength
-19%
Elongation at break -22%
Not self-extinguishing.
Burning rate approx. 2 cm/
min. Conforms to require-
ments for use in car bodies.
Normally resistant to:
Detergents
Highly oxidizing chemicals
such as:
Ammonia
Dilute phosphoric acid
Dilute cromic acid
Dilute nitric acid
Dilute hydrochloric
Dilute sulphuric acid
Other chemicals such as
Film developer
Glycol
Cutting fluid (emulsion)
Only slightly affected by:
Concentrated acids at room
temperature
CR
TET-C
Black
Weather and temperature
resistant. Can be used both
indoors and outdoors.
For continuous use between
-25°C and +95°C. Some-
what higher temperature
for short periods of time.
After 72 hours at +100°C.
Property changes:
Hardness +6 ° Shore
(+10%)
Ultimate tensile strength
-8%
Elongation at break -16%
After 72 hours at +125°C.
Property changes:
Hardness +13 ° Shore
(+13%)
Ultimate tensile strength
-12%
Elongation at break -35%
Self-extinguishing.
Tested as per IEC standard.
Approved for installation
on ships.
Normally resistant to:
Aliphatic hydrocarbons
Alkalies
Alcohols
Dilute acids
Only slightly affected by:
Acetone
Ammonia
Freon
Glycol
Sodium hydroxide
Good resistance to mineral
oils. Other petroleum pro-
ducts such as grease and
wax have very little effect.
But should not be used in
direct contact with petrol
(gasoline).
PEH
1)
TCF
Grey
Weather and temperature
resistant. Can be used both
indoors and outdoors.
For continuous use between
-25°C and +80°C.
Tested to glowire standard
DIN 57471 section 2 (75),
VDE 0471 section 2/4.75
and EdF HN 60EO1 with
750°C.
Normally resistant to:
Aliphatic hydrocarbons
Alkalies
Alcohols
Dilute acids
Only slightly affected by:
Acetone
Ammonia
Freon
Glycol
Sodium hydroxide
Good resistance to mineral
oils. Other petroleum pro-
ducts such as grease and
wax have very little effect.
But should not be used in
direct contact with petrol
(gasoline).
1) Seal: Clorophene (CR). Tests: See TET-C.
All figures given in the table above are indicated values on laboratory tests. Factors such as temperature, length of exposure, concentration etc., have great effect on the properties of the materials.
Feel free to contact us if you are not certain which grade you should choose.
PA (Glass Fibre Rein-
forced)
1)
TCG Grey
Weather and temperature
resistant. Can be used both
indoors and outdoors.
For continuous use between
-25°C and +80°C.
Not self-extinguishing.
Normally resistant to:
Aliphatic hydrocarbons
Alkalies
Alcohols
Dilute acids
Only slightly affected by:
Acetone
Ammonia
Glycol
Sodium hydroxide
Good resistance to mineral
oils. Other petroleum pro-
ducts such as grease and
wax have very little effect.
But should not be used in
direct contact with petrol
(gasoline).