Datasheet

Product data sheet
Characteristics
VCF2GE
TeSys Vario enclosed
Main
Range TeSys
Product name TeSys VARIO
Device short name VCF
Product or component type Enclosed emergency stop switch disconnector
Performance level High performance
Poles description 3P
Control type Rotary handle
Handle colour Red
Handle front plate colour Yellow
Rotary handle padlocking 1 to 3 padlocks with 4...8 mm
Complementary
Marking 0 - 1
[Ue] rated operational voltage 690 V AC
[Uimp] rated impulse withstand voltage 8 kV
[Ithe] conventional enclosed thermal
current
32 A
[Ie] rated operational current 29 A AC-23A 400 V
Rated operational power in W 11 kW at 400 V AC-3
15 kW at 400 V AC-23
Intermittent duty class 30
Making capacity ( I rms) 400 A at 400 V AC-21A
400 A at 400 V AC-22A
400 A at 400 V AC-23A
[Icm] rated short-circuit making
capacity
1 kA at 400 V at Ipeak
[Icw] rated short-time withstand Rms
current
480 A at 400 V during 1 s
Rated conditional short-circuit current 10 kA at 400 V - associated fuse 50 A aM
10 kA at 400 V - associated fuse 50 A gG
Breaking capacity 320 A at 400 V (AC-21A)