12. IO Scanning service
12. 1. Presentation
The IO Scanning service is used to exchange periodic I/O data between:
A controller or PLC (IO Scanner).
Devices (IO Scanning servers).
This exchange is usually performed by implicit services, thus avoiding the need to program the controller (PLC).
The IO Scanner periodically generates the Read/Write Multiple Registers (23 = 16#17) request.
The IO Scanning service operates if it has been enabled in the PLC and the drive.
The drive parameters assigned to IO Scanning have been selected by default. This assignment can be modified by configuration.
The table below indicates the tools which can be used to modify these configurations:
The drive IO Scanning service can also be configured by the Ethernet card Modbus server.
When the IO Scanning service has been enabled in the Altivar 61/71 drive:
A TCP connection is assigned to it.
The parameters assigned in the periodic variables are exchanged cyclically between the Ethernet card and the drive.
The parameters assigned to the periodic output variables are reserved for IO Scanning. They cannot be written by other Modbus services,
even if the IO Scanner is not sending its periodic output variables.
12. 2. Periodic variables
It is possible to configure the assignment of periodic variables 1 to 10.
Functions Graphic display
terminal
Integrated
display
terminal
PowerSuite
software
workshop
Standard
web server
Enable IO Scanning pppp
Configuring the IO Scanning variables pp
Output variables (written by IO Scanner) Input variables (read by IO Scanner)
No. Meaning/default assignment Configurable No. Meaning/default assignment Configurable
0 Reserved no 0 Reserved no
1 Control word (CMd) yes 1 Status word (EtA) yes
2 Speed setpoint (LFrd) yes 2 Output speed (rFrd) yes
3 Not assigned yes 3 Not assigned yes
4 Not assigned yes 4 Not assigned yes
5 Not assigned yes 5 Not assigned yes
6 Not assigned yes 6 Not assigned yes
7 Not assigned yes 7 Not assigned yes
8 Not assigned yes 8 Not assigned yes
9 Not assigned yes 9 Not assigned yes
10 Not assigned yes 10 Not assigned yes
11-31 Reserved no 11-31 Reserved no
Note: Avoid configuring the drive configuration parameters as periodic output variables because they cannot be modified with the
motor running (DSP 402 state 5—"Operation Enabled”).
Monitoring parameters must not be configured as periodic output variables, because they cannot be written.