Installation manual

Installation
3–12 152936
This manual is for use by qualified personnel only.
PV Array Connections
To make the connections from the PV Array/combiner to DC Interface
Enclosure:
1. Open the door to the DC Interface Enclosure.
2. Route the PV Array cables conductors POSitive (PV+) and NEGative (PV-)
through the conduit to the DC Interface Enclosure, entering on the underside.
3. The DC power conductor terminations are made at the PV+, and PV-
allocations and the ground bar. See Figure 3-11.
4. Terminations for the POSitive, NEGative, and PE (ground) conductors within
the DC Interface Enclosure are made using the 12 mm hardware.
5. Close the door to the DC Interface Enclosure.
Figure 3-11 PV Array Cable Routing and Terminations
PV+
PV-