Specifications

Introduction
1–4 975-0581-01-01
This manual is for use by qualified personnel only
3 stand-by/power-on Switch
The Xantrex inverter incorporates a maintained position 3 (stand-by/power-on)
switch (called
ON/OFF on older models) located on the right center door, under
the main control display. Under normal conditions, the 3 (stand-by/power-on)
switch is in the 2 (power-on) position. Turning the switch to the 1 (stand-by)
position initiates an immediate controlled shutdown of the Xantrex inverter and
opens both the main AC contactor and DC disconnect switch within the unit.
Turning the switch to the 1 (stand-by) position will not de-energize unit; it only
stops power production. The main AC contactor and DC disconnect switch
cannot be closed unless the switch is in the 2 (power-on) position. The Xantrex
inverter is prevented from being restarted until the 3 (stand-by/power-on) switch
is turned back to the 2 (power-on) position.
Figure 1-2 3 stand-by/power-on Switch