Specifications

Wiring - Specific
975-0581-01-01 3–11
This manual is for use by qualified personnel only
1000 Vdc Input Option
If you have a Xantrex GT630 E with 1000 Vdc input option your inverter is
configured with the following pre-installed conductors:
1 cable with cross section of 35mm² (coming from PV+)
3 cables with cross section of 10mm² coming from the chopper IGBT's
These conductors are located cabinet +H2, coiled on the bottom. You must
connect these wires to the resistor that was installed in the sub-floor of the
concrete PV box or pad as described on page 2–3.
Uninterruptable Power Supply Installation
If you have a Xantrex GT500 E or Xantrex GT630 E with optional ride-through
capability you need to install a UPS for operation. You can order an appropriate
UPS from Schneider Electric (part number: 820-0031-01-01) if you are using
230 Vac auxiliary supply voltage in your installation, or you can use any UPS
which meets the requirements in Table A-7 on page A–5 and matches the
auxiliary supply voltage for your installation.
Refer to Figure 3-7 and Figure 3-8 to locate the connection points.