Specifications

Advanced Troubleshooting
5–8 975-0581-01-01
This manual is for use by qualified personnel only
0040 Programming
Software
S This code indicates that the
Xantrex inverter has detected
that the system is in
Programming mode. This fault
does not indicate any
malfunction with the Xantrex
GT500 E & Xantrex GT630 E, but
is merely an indication that the
system software is in the process
of being downloaded into the
EEPROMs of the control unit.
0041 State Invalid S The state machine implemented
within the control unit system
software governs the operation of
the Xantrex GT500 E & Xantrex
GT630 E. This fault indicates that
the Xantrex inverter has detected
an unknown system variable and
has encountered an invalid state.
Internal RAM error
•CPU error
0042 Serial EEPROM
Write Error
S This fault indicates that the
Xantrex inverter has detected a
serial EEPROM write error. The
control unit controller board
performs a verification check of
data written to ROM compared to
what is read back.
Internal ROM error
•CPU error
0043 Serial EEPROM
Timeout
S This fault indicates that the
Xantrex inverter has detected
that when writing data to the
serial EEPROM, a confirmation
timer of 300mS has expired.
Internal ROM error
•CPU error
0044 Bad NOVRAM
Memory
S This fault indicates that the
Xantrex inverter has detected
that one of the two non-volatile
memory banks on the control unit
controller board has failed. The
control unit performs a series of
tests to confirm the validity of the
NOVRAM, and one of the two
banks has produced errors.
Internal NOVRAM
error
•CPU error
Table 5-1 Fault Codes
Error
Code Fault Source(s)
Fault Type
H=Hardware
S=Software Fault Description Possible Causes