Specifications

Specifications
A–4 975-0581-01-01
This manual is for use by qualified personnel only
Regulatory Specifications
Regulatory specifications for the Xantrex inverter are as follows:
CE marked for the Low Voltage Directive per EN50178
CE marked for the EMC Directive per EN61000-6-4 (emissions) and
EN61000-6-2 (immunity)
Complies with RD1663/2000 and 661/2007 (Spain)
Complies with Decree from 23 April 2008; “Arêté du 23 Avril 2008” (France)
Low voltage ride-through version complies with BDEW medium voltage grid
connection requirement; "Technische Richtlinie - Erzeugungsanlagen am
Mittelspannungsnetz, BDEW, June 2008" (Germany)
Bureau Veritas certificate for DK5940 (Italy)
Over Voltage, Under Voltage and Frequency Ranges
Table A-4 provides the over-voltage, under-voltage, over-frequency, and under-
frequency detection limits for the Xantrex inverter. These detection limits have
been tested and are in compliance with requirements given under Regulatory
Specifications above.
Table A-4 Over/Under-Voltage and Over/Under-Frequency Ranges
AC Voltage Condition
(% of Nominal) Xantrex GT500 E Xantrex GT630 E
Low Range
85%
Vac 105%
5% Vac 105%
a
a.values are for all units with the optional low voltage ride-through capability installed
267.75 Vac 330.75
15.75
Vac 330.75
318.75
Vac 393.75
18.75
Vac 393.75
Low Default
90% = Vac
Vac = 283.5 Vac = 337.5
High Range
97% Vac 115%
305.55 Vac < 362.25 363.75 Vac 431.25
High Default
110% = Vac
Vac = 346.5 Vac = 412.5
50 Hz Low Range
-3.0 Hz f +0.5 Hz
47.0 f 50.5 47.0 f 50.5
50 Hz Low Default f = 49.0 f = 49.0
50 Hz High Range
-0.5 Hz f +3.0 Hz
49.5 f 53.0 49.5 f 53.0
50 Hz High Default f = 51.0 f = 51.0
60 Hz Low Range
-5.0 Hz f +0.5 Hz
55.0 f 60.5 55.0 f 60.5
60 Hz Low Default f = 59.5 f = 59.5
60 Hz High Range
-0.5 Hz f +5.0 Hz
59.5 f 65.0 59.5 f 65.0
60 Hz High Default f = 60.5 f = 60.5