Specifications
System Specifications
975-0581-01-01 A–5
This manual is for use by qualified personnel only
Bolt Sizes and Torque Requirements
Table A-5 provides acceptable bolt sizes and torque values for AC terminal
connections.
Table A-6 provides acceptable bolt sizes and torque values to be connected to
the Xantrex inverter’s DC terminal connections.
Uninterrupted Power Supply – UPS
If you have a Xantrex GT500 E or Xantrex GT630 E with optional ride-through
capability you need to install a UPS for operation. You can order an appropriate
UPS from Schneider Electric (part number: 820-0031-01-01) if you are using
230 Vac auxiliary supply voltage in your installation, or you can use any UPS
which meets the requirements in Table A-7 and matches the auxiliary supply
voltage for your installation.
Table A-5 AC Terminal Bolt Size, and Torque Values
AC Terminal
Connections
Max. # of Conductors
per Terminal
Bolt
(Hardware) Size
Torque
Requirements
PE (Enclosure Ground) 2 1/M12 75 Nm
(55 lb ft)
L1, L2, L3 6 3/M12 75 Nm
(55 lb ft)
-X2:L1, -X2:L2 to AC aux input
transformer
1 cable cross section 0.5 - 10 mm²
use appropriate ferrules
0.6 – 0.8 Nm
(5.3 – 7.1 lb ft)
-X2:23 and -X2:25 to UPS input,
-X2:24 and -X2:26 to UPS output
1 cable cross section 0.5 - 10 mm²
use appropriate ferrules
0.5 – 0.6 Nm
(4.4 lb ft– 5.3 lb ft)
X2:6 and X2:7
(external interlock)
1 cable cross section: 0.14 - 2.5 mm²
use appropriate ferrules
X2:20 and X2:22
(external voltage)
1 cable cross section 0.5 - 10 mm²
use appropriate ferrules
Table A-6 DC Terminal Bolt Size, and Torque Values
DC Terminal
Connections
Max. # of Conductors
per Terminal
Bolt
(Hardware) Size
Torque
Requirements
PV+, PV- 8 8/M12 75 Nm
(55 lb ft)
Table A-7 Minimum UPS Specifications
Power 500 VA
AC Input must match auxiliary supply voltage provided by
the installer (230, 315, or 400 Vac)
AC Outputs 230 V
Use UPS in bypass operation:
Cross-over Time < 10 msec
Support Time > 5 sec