Xantrex™ GT100 E 100 kW Grid-Tied Photovoltaic Inverter Planning and Installation Manual www.schneider-electric.
Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter Planning and Installation Manual www.schneider-electric.
Copyright and Contact Trademarks Schneider Electric, the Schneider Electric logo, and Xantrex are trademarks or registered trademarks of the Schneider Electric group of companies. Other trademarks, registered trademarks, and product names are the property of their respective owners and are used herein for identification purposes only. Notice of Copyright Copyright © 2008, 2009, 2010 Xantrex Technology Inc. All rights reserved.
About This Manual Purpose The purpose of this Planning and Installation Manual is to provide explanations and procedures for planning and installing the Schneider Electric Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter. For information on Operating or Troubleshooting the inverter, refer to the Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter Operation and Maintenance Manual (Part # 152365).
About This Manual Conventions Used The following conventions are used in this guide. WARNING Warnings identify conditions or practices that could result in personal injury or loss of life. CAUTION Cautions identify conditions or practices that could result in damage to the unit or other equipment. Important: These notes describe things which are important for you to know, but not as serious as a caution or warning. iv 152364 This manual is for use by qualified personnel only.
About This Manual Abbreviations and Acronyms AC Alternating Current ANSI American National Standards Institute BTU British Thermal Unit CCU2 Converter Control Unit 2 CFM Cubic Feet per Minute CW Clockwise DC Direct Current DSP Digital Signal Processor FPGA Field Programmable Gate Array GUI Graphical User Interface IEEE Institute of Electrical and Electronics Engineers IGBT Insulated Gate Bipolar Transistor IPM Intelligent Power Module kcmil 1000 circular mils LAN Local Area Net
vi
Important Safety Instructions SAVE THESE INSTRUCTIONS - DO NOT DISCARD This manual contains important safety instructions for the Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter (Xantrex GT100 E) that shall be followed at all times. WARNING: Exercise extreme caution Read and keep this Planning and Installation Manual for future reference. Before using the Xantrex GT100 E, read all instructions, cautionary markings, and all other appropriate sections of this manual.
Safety Risks WARNING: Shock hazard Parts of the condenser charge will still be energized for a maximum of 20 minutes after being disconnected. Open device cover plates or doors only after the device is disconnected and discharged. Check whether the device is no longer live (DC voltage) including terminals PV+ and PV-. WARNING: Explosion hazard The IGBT module may explode in the event of a major malfunction. Do not operate larger devices while the pivoting part is opened.
Safety General Safety Precautions 1. When installing the Xantrex GT100 E use only components recommended or sold by Schneider Electric. Doing otherwise may result in a risk of fire, electric shock, injury to persons, and will void the warranty. 2. Do not attempt to operate the Xantrex GT100 E if it has been dropped, or received more than cosmetic damage during transport or shipping.
Safety Wiring Requirements WARNING: Fire hazard In accordance with the National Electrical Code, ANSI/NFPA 70, connect only to a circuit provided with 200 amperes maximum branch circuit overcurrent protection. 1. All wiring methods and materials shall be in accordance with the European Requirements, as well as all state and local code requirements (for example, DIN / VDE). 2. The Xantrex GT100 E has a three-phase output. 3.
Safety Lockout and Tag WARNING: Shock hazard Review the system schematic for the installation to verify that all available energy sources are de-energized. DC bus voltage may also be present. Be sure to wait the full 20 minutes to allow the capacitors to discharge completely. Schematics are located inside the front door of the unit. Safety requirements mandate that this equipment not be serviced while energized. Power sources for the Xantrex GT100 E must be locked-out and tagged prior to servicing.
Safety De-Energize/Isolation Procedure WARNING: Shock hazard The terminals of the DC input may be energized if the PV arrays are energized. In addition, allow 5 minutes for all capacitors within the main enclosure to discharge after disconnecting the Xantrex GT100 E from AC and DC sources. The following procedure should be followed to de-energize the Xantrex GT100 E for maintenance. To isolate the Xantrex GT100 E: 1. Turn the ON/OFF switch to the OFF position. 2.
Contents Important Safety Instructions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - vii 1 Introduction Description of the Xantrex GT100 E - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 Operator Interface Controls - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3 ON/OFF Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Contents PV Array Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - AC Line Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Ground Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Cable Installation (Optional) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Auxiliary Fan Power C
Figures Figure 1-1 Figure 1-2 Figure 1-3 Figure 1-4 Figure 1-5 Figure 2-1 Figure 2-2 Figure 2-3 Figure 3-1 Figure 3-2 Figure 3-3 Figure 3-4 Figure 3-5 Figure 3-6 Figure 3-7 Figure 3-8 Figure 3-9 Figure A-1 Xantrex GT100 E Operator Interface Components- - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3 ON/OFF Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4 Emergency Stop- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
xvi
Tables Table A-1 Table A-2 Table A-3 Table A-4 Table A-5 Table A-6 Table A-7 Table A-8 Environmental Specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Electrical Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Regulatory Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Torque Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
xviii
1 Introduction Chapter 1, “Introduction” provides information about the features and functions of the Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter. This manual is for use by qualified personnel only.
Introduction Description of the Xantrex GT100 E The Schneider Electric Model Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter is a single enclosure, three-phase power conversion system for gridconnected photovoltaic arrays with a rating of 100 kW. The Xantrex GT100 E inverter incorporates the innovative switching technology utilizing state-of-the-art IPMs (Intelligent Power Module), to convert the photovoltaic array's DC power to the utility's three-phase AC power.
Operator Interface Controls Operator Interface Controls WARNING: Shock hazard Turning the ON/OFF switch to the OFF position does not remove all hazardous voltages from inside the inverter. Before attempting to service the Xantrex GT100 E, follow the de-energize Lockout and Tag procedure on page xi.
Introduction ON/OFF Switch WARNING: Shock hazard Turning the ON/OFF switch to the OFF position does not remove all hazardous voltages from inside the inverter. Before attempting to service the Xantrex GT100 E, follow the de-energize Lockout and Tag procedure on page xi. The Xantrex GT100 E incorporates a maintained position ON/OFF switch located on the front door of the inverter enclosure. Under normal conditions, the ON/OFF switch is in the ON position.
Operator Interface Controls Emergency Stop (E-STOP) The Xantrex GT100 E incorporates a maintained position E-STOP pushbutton located on the inverter enclosure. Under normal conditions, the E-STOP pushbutton is in the CLOSED (extended) position. Pushing the pushbutton to the OPEN (depressed) position will initiate an immediate controlled shutdown of the Xantrex GT100 E and open both the main AC and DC contactors within the unit.
Introduction AC Disconnect Switch WARNING: Shock hazard Disengaging the inverter enclosure door interlock switch does not remove all hazardous voltages from inside the inverter. Before attempting to service the Xantrex GT100 E, follow the de-energize Lockout and Tag procedure on page xi. The AC disconnect switch is the primary disconnect for the inverter. The inverter’s doors cannot be opened until the AC disconnect switch is in the OFF position.
Operator Interface Controls Front Panel User Interface The Xantrex GT100 E has a front panel user interface which is comprised of a 4-line display screen for reporting basic system status and all fault conditions plus a keypad for configuration. The keypad is comprised of 20 touch-sensitive keys that provide a means to navigate through the menus and alter userchangeable settings.
Introduction Communication Features and Methods The Xantrex GT100 E provides two types of information to the user: • system status and/or fault information, and • data logging information. System status and fault information can be accessed using the user interface keypad and display or a personal computer using the PV View GUI (Graphic User Interface) software. Data logging requires the use of a PC using the PV View.
Communication Features and Methods Data Logging The inverter stores data values and software metrics for debugging. These values are stored within the CCU2 controller board in non-volatile memory. Data logging requires the use of a PC connection using the PV View.
Introduction Optional Equipment The following options are available for purchase for use with the Xantrex GT100 E to enhance its communications capability. The additional Xantrex GT100 E options can be field installed. Contact a Schneider Electric distributor for further information on installation options. External Analog Input Requirements The Xantrex GT100 E has an option for measuring external devices through its 4 analog input lines.
2 Planning Chapter 2, “Planning” provides information to help plan the installation of the Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter. This manual is for use by qualified personnel only.
Planning Overview of Xantrex GT100 E Installation WARNING: Shock hazard Installations of this equipment should only be performed by qualified technicians. Installers must meet all local and state code requirements for licensing and training for the installation of Electrical Power Systems with AC and DC voltage to 650 volts.
Environmental Requirements Environmental Requirements The following environmental conditions must be established and maintained to ensure the safe and efficient operation and servicing of the Xantrex GT100 E. • Maintain a minimum clearance of 31 cm (12 in,) plus local safety requirements in front and back of the enclosure for air intake, fan cooling, maintenance and serviceability. • External cabling enters the Xantrex GT100 E from the bottom.
Planning Utility Side Isolation Transformer Requirements WARNING: Lethal voltage Grounding the neutral of a Wye-wound transformer may create an “open delta” condition, depending on the utility configuration. This condition may keep the Xantrex GT100 E from detecting a loss of phase condition on the utility system, which may allow potentially lethal voltage to be present on the open-phase wiring.
Electrical Diagrams Figure 2-1 Xantrex GT100 E Electrical Diagram 152364 2–5 This manual is for use by qualified personnel only.
Planning Conduit Entry Figure 2-2 shows the maximum allowable area and location in which electrical conduits may penetrate the enclosures of the Xantrex GT100 E. All measurements in mm Figure 2-2 Enclosure Conduit Entries, Bottom Side View 2–6 152364 This manual is for use by qualified personnel only.
Anchoring the Xantrex GT100 E Anchoring the Xantrex GT100 E The Xantrex GT100 E is designed to be installed in an indoor location. It must be placed on and anchored to a level concrete floor or pad. The concrete floor or pad, upon which the Xantrex GT100 E is anchored, must be structurally designed to meet any local, state, or national requirements for weight, seismic, and wind sheer if applicable. Twelve 16 mm holes are provided in the feet of the enclosure for anchoring to the floor or pad.
2–8
3 Installation Chapter 3, “Installation” describes the procedures needed to install the Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter. This section includes unpacking and moving instructions, mounting instructions, and cabling instructions. This manual is for use by qualified personnel only.
Installation Unloading WARNING: Heavy equipment The Xantrex GT100 E weighs 870 kg. Attempting to lift the equipment by other than the recommended lifting points may damage the equipment or present a personnel safety hazard and void the warranty. Keep the doors closed and latched when moving the inverter enclosures. Leaving the door latches unsecured may result in damage to the unit and void the warranty.
Moving Instructions Unpacking the Xantrex GT100 E To unpack the Xantrex GT100 E from the shipping crate: 1. Remove the crate’s wood side and top panels. 2. Remove the barrier bag material from the inverter. 3. Remove the inverter’s anchor hardware that bolts the inverter to the pallet. Moving Instructions To move the Xantrex GT100 E using a forklift: 1. Place the forks of the forklift below the unit at the points specified in Figure 32. 2. Lift the Xantrex GT100 E from beneath the enclosure.
Installation To move the enclosure using the lifting eyebolts: 1. Place the lifting straps onto the eyebolts as shown in Figure 3-3. All four-corner eyebolts must be evenly loaded. 2. Strap the unit such that the angle between the sling and the cabinet top is greater than 60 degrees. 3. Remove the pallet from underneath the unit Figure 3-3 Eyebolt Lifting Locations - From Above Unit 3–4 152364 This manual is for use by qualified personnel only.
Mounting and Anchoring the Units Mounting and Anchoring the Units To mount and anchor the Xantrex GT100 E: 1. Predrill the floor or pad to accept masonry anchors for 12 mm bolts, or ensure it has pre-installed anchoring bolts that will fit the 18 mm mounting holes. See Figure 2-3 on page 2–7. 2. Lift the Xantrex GT100 E from beneath with a forklift or pallet jack as shown in Figure 3-2 on page 3–3, or lift the Xantrex GT100 E from above as shown in Figure 3-3 on page 3–4.
Installation Wiring - General All wiring methods and materials shall be in accordance with the National Electrical Code ANSI/NFPA 70, European Requirements, as well as all state and local code requirements (for example, DIN / VDE). When sizing conductors and conduits interfacing to the Xantrex GT100 E, both shall be in accordance with the National Electric Code ANSI/NFPA 70, European Requirements, as well as all state and local code requirements (for example DIN / VDE).
Wiring - General Overcurrent Protection CAUTION: Equipment damage In accordance with the NEC, ANSI/NFPA 70 (Ninth Edition) the following branchcircuit overcurrent protection must be provided: • 200A maximum Unless provided as part of the Schneider Electric supplied equipment; the AC overcurrent protection for the utility interconnect (Grid-tie) must be provided by the installer as part of the Xantrex GT100 E installation.
Installation Grounding Install a copper ground rod within 1 m (3 ft.) of the Xantrex GT100 E enclosures per the National Electric Code ANSI/NFPA 70. The single-point ground for the system is to be made at the ground bar (TB1) in the main inverter enclosure. The chassis ground is made at the same bus bar in the main inverter enclosure (TB1) and has a 12 mm bolt for terminating the DC ground. The ground conductor size depends on the size of the main circuit breaker. NEC Table 250.
Xantrex GT100 E Connections Xantrex GT100 E Connections Use the following descriptions and figures to correctly identify access panels and route wiring. Input/Output Access Base Panels Install all the conduits needed for cable entry in the access base panels, see Figure 3-6. Figure 3-6 Access Panel Locations 152364 3–9 This manual is for use by qualified personnel only.
Installation PV Array Connections WARNING: Fire hazard To reduce the risk of fire, connect only to a circuit provided with 200 amperes maximum branch circuit overcurrent protection. CAUTION: Equipment damage When connecting external AC wires to the Xantrex GT100 E, positive phasing sequence must be maintained throughout the installation process.
Xantrex GT100 E Connections AC Line Connections To connect the AC line: 1. Route the line AC (A, B, C and N) cables through the base access panel. 2. Connect the cables to terminals on the AC disconnect switch respectively, see Figure 3-8. 3. Secure the AC line cables to the tie wrap mounting terminals using appropriate tie wraps. Ground Bar (TB1) AC Line (N) AC Line (C) AC Line (B) AC Line (A) Figure 3-8 Line Cable Routing Ground Connections To connect the ground: 1.
Installation Cable Installation (Optional) Auxiliary Fan Power Connection To connect power to the auxiliary fan: 1. Remove the two jumpers on TB3 pins 1-2 and pins 2-3 located on the operator interface panel. 2. Route the auxiliary AC line, neutral and ground wires through the base access panel and connect the wires to the terminal block TB3, AC line to TB3-2, AC neutral to TB3-4, and ground to TB3-5, see Figure 3-9.
4 Verification and Commissioning Chapter 4, “Verification and Commissioning” provides a method for ensuring the installation of the Xantrex GT100 E is correct and complete and provides commissioning procedures. This manual is for use by qualified personnel only.
Verification and Commissioning System Verification WARNING: Lethal voltage This chapter describes specific steps to ensure the installation of the Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter is correct and complete. Failure to adhere to these warnings could result in severe shock or possible death. Exercise extreme caution at all times to prevent accidents. These installation instructions are for use by those familiar and skilled with high voltage procedures.
System Verification 3. Visually inspect the utility transformer connections. If the inverter-side winding of the transformer is configured Wye; ensure the transformer neutral connection is left disconnected or floating. The neutral connection of the transformer must be left disconnected or floating or damage to the inverter will occur. 4. Perform corrective actions if required. To perform a system verification of the Xantrex GT100 E: 1. Verify 400 Vac voltage across the bottom of the AC disconnect switch.
Verification and Commissioning Commissioning Procedure Important: It is important to record any issues encountered while following this procedure. This section provides the procedure necessary to safely and correctly commission a Xantrex GT100 E inverter. To commission the Xantrex GT100 E: 1. Ensure the system verification tests have been completed and have passed successfully. 2. Begin the Xantrex GT100 E commissioning procedure as described in detail further in this section.
Starting the Commissioning Test Starting the Commissioning Test Enter the information required on the form in Appendix B, “Commissioning Test Record”. The converter serial number is located on a label placed on the lowerleft front of the inverter enclosure door. To inspect the inverter enclosure: 1. Open both doors of the Xantrex GT100 E inverter enclosure and inspect the connections. 2. Check for loose cables, rubbing, or interference. 3. Correct and record any defects. To verify AC voltage: 1.
Verification and Commissioning To verify the front panel display: 1. Open then close the AC disconnect and look at the front panel display. It displays the software versions both of the CCU2 and front panel within the read menu. Record these numbers. 2. After about 20 seconds the Xantrex GT100 E is in “ready” mode. If any alarms are present, refer to the Troubleshooting Chapter in your Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter Operation and Maintenance Manual (Part # 152365). 3.
Starting the Commissioning Test 7. Check all the operating data with the GUI or front panel. Record any irregularities. 8. Let the inverter run. 9. Verify the matrix fans operate after the matrix temperature reaches at least 30°C, and the "INV kW" is at least 30 kW. To complete the commissioning: 1. Once you have successfully completed all the commissioning steps, ensure all the information is documented. 2. Fax a copy of the product registration form to Schneider Electric.
4–8
A Specifications Appendix A contains the specifications for the Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter. The Xantrex GT100 E has been designed for photovoltaic power systems, which operate within the following specifications. Application of the Xantrex GT100 E in a manner inconsistent with these specifications may cause damage to the Xantrex GT100 E and other system components, and is a violation of the terms of the warranty. Specifications are subject to change.
Specifications System Specifications The Xantrex GT100 E has been designed for photovoltaic power systems, which operate within the following specifications. CAUTION: Equipment damage Operation of the Xantrex GT100 E in a manner other than specified in this manual may cause damage to the Xantrex GT100 E and other system components and will void the terms of the warranty. Environmental Specifications CAUTION: Environmental damage The Xantrex GT100 E will be destroyed if stored outside.
System Specifications Regulatory Specifications Table A-3 provides the regulatory specifications for the Xantrex GT100 E. Table A-3 Regulatory Specifications Standard Regulation Met General Standards EN50178 VDEW CE Emitted Interference EN61000-6-4 Interference Resistance EN61000-6-2 Torque and Wire Gauge Specifications Use the following torque specifications on all electrical interfaces made during installation of the Xantrex GT100 E.
Specifications The Xantrex GT100 E has the option to connect an external fan control contactor/ unit to the unit, TB4. Table A-8 External Fan Control Requirements External Fan Control Voltage TB4 5-6 230 Vac +10%-12% Maximum External Fan Control Current TB4 5-6 2 Amps Dimensions Dimensions in mm Figure A-1 Xantrex GT100 E Dimensions A–4 152364 This manual is for use by qualified personnel only.
B Commissioning Test Record Appendix B, “Commissioning Test Record” contains the form to be filled out in order to keep a record of the commissioning test results for the Xantrex GT100 E 100 kW Grid-Tied Photovoltaic Inverter. This manual is for use by qualified personnel only.
B–2
Commissioning Test Record Commissioning Test Record Step 1. Record and Document Serial Number and Inverter Location Date and Time of Commissioning: Inverter Serial Number: Technician Name: CCU2 Board Serial Number: Company Name: Inverter Location: Bldg. # Contact Email: Address: City: State: Step 2. Installation and Cable Check Power Conductors installed correctly: Yes Terminations are properly torqued: Yes Step 3.
B–4
CE Declaration of Conformity CE Declaration of Conformity 152364 B–5 This manual is for use by qualified personnel only.
B–6
Schneider Electric www.schneider-electric.com ☎ North America 1 408 987 6255 ✉ 1 925 245 1022 re.techsupport@schneider-electric.com France 0 825 012 999 fr-re-techsupport@fr.schneider-electric.com Deutschland +49 (0) 180 575 6575 +49 (0) 2102 404 7101 solarservice@de.schneider-electric.com España +34 93 498 7466 +34 93 305 5026 re.techsupport@es.schneider-electric.com L'Italia +39 035 4151111 +39 035415 3200 IT-pronto-contatto@it.schneider-electric.