Operator Interface Controls
152364 1–5
This manual is for use by qualified personnel only.
Emergency Stop (E-STOP)
The Xantrex GT100 E incorporates a maintained position E-STOP pushbutton
located on the inverter enclosure. Under normal conditions, the E-STOP
pushbutton is in the CLOSED (extended) position. Pushing the pushbutton to the
OPEN (depressed) position will initiate an immediate controlled shutdown of the
Xantrex GT100 E and open both the main AC and DC contactors within the unit.
The main AC and DC contactors cannot be closed unless the pushbutton is in
the CLOSED (extended) position. The Xantrex GT100 E is prevented from being
restarted until the E-STOP pushbutton is in the CLOSED (extended) position.
Provisions are supplied for adding a remote emergency stop circuit.
Figure 1-3 Emergency Stop