Specifications
A–2 152364
This manual is for use by qualified personnel only.
System Specifications
The Xantrex GT100 E has been designed for photovoltaic power systems, which
operate within the following specifications.
Environmental Specifications
Electrical Specifications
Table A-2 provides the AC and DC specifications for the Xantrex GT100 E.
CAUTION: Equipment damage
Operation of the Xantrex GT100 E in a manner other than specified in this manual
may cause damage to the Xantrex GT100 E and other system components and
will void the terms of the warranty.
CAUTION: Environmental damage
The Xantrex GT100 E will be destroyed if stored outside. Only store in dry areas.
Table A-1 Environmental Specifications
Operating Temperature
-10
a
to 45° C
a.If ambient temperature is between -10 to 0° C, the unit must be powered up in standby for at
least one hour prior to going on-line.
Storage Temperature -40 to 50° C
Maximum Ambient Temperature Rating 45° C
Relative Humidity To 90%, Non-condensing
Elevation Derated above 2000 m
Dimensions (mm) 1905 x 1205 x 606
Weight 870 kg
Enclosure Type IP21
Table A-2 Electrical Specifications
Nominal AC Line Voltage 400 Vac (+10%/-12%)
Maximum AC Line Current 164 ARMS (at low line voltage)
Nominal Line Frequency 50 Hz, +0.5 -0.7 Hz
Output Power 100.0kW
Max. Open Circuit Voltage 650 Vdc
Peak Power Tracking Window 300-650 Vdc
PV Minimum Peak Power Tracking Voltage 300 Vdc
Maximum PV Current 347 ADC