System Specifications
152364 A–3
This manual is for use by qualified personnel only.
Regulatory Specifications
Table A-3 provides the regulatory specifications for the Xantrex GT100 E.
Torque and Wire Gauge Specifications
Use the following torque specifications on all electrical interfaces made during
installation of the Xantrex GT100 E.
The following table shows acceptable wire sizes to be connected to the Xantrex
GT100 E 100 kW Grid-Tied Photovoltaic Inverter AC and DC inputs.
Specifications for Options
The Xantrex GT100 E has the Option to connect an external AC line to power the
internal fans of the unit, TB3.
The Xantrex GT100 E has the option to connect to an external remote emergency
switch to the unit, TB4.
Table A-3 Regulatory Specifications
Standard Regulation Met
General Standards EN50178
VDEW
CE
Emitted Interference EN61000-6-4
Interference Resistance EN61000-6-2
Table A-4 Torque Requirements
Type Torque Setting
AC Terminal Lugs – 8mm Hex 20.0Nm
M10 Bolt (DC + and DC-) 40.0Nm
Table A-5 Terminations and Wire Requirements
Terminal-Connections Wire Size
AC Terminal Lugs
Up to 120 mm
2
Compression Lug (DC+ and DC-)
Up to 300 mm
2
Table A-6 Auxiliary AC Line Requirements
Nominal Aux. AC Line Voltage 230 Vac, +10%-12%
Maximum Aux. AC Line Current 4 Amps
Table A-7 Remote Emergency Switch Requirements
Remote Emergency Switch No external power applied to the TB4 1 -4