Installation manual
Safety
xiv 975-0601-01-01 Revision B
This manual is for use by qualified personnel only.
12. Open the inverter assembly’s right door only.
13. Wearing appropriate personal protective equipment and using a voltmeter
with minimum ratings of 1000 volts AC and DC that has been tested on a
known AC voltage source and a known DC voltage source before use,
measure DC voltage from line to line and from line to ground (see Figure ii):
• Between the PV+ bus bar and the PV- bus bar and to ground to make
sure the inverter side of the DC switch is de-energized.
• Between the terminals of F5 and F6 and to ground to make sure the DC
input side of the DC switch is de-energized. Measure only from the top of
the F5 and F6 fuse holders. Measuring from the bottom could result in a
false reading.
Do not proceed until the voltage has decreased to 0 VDC.
NOTICE
Use the support bar for the bus bars as the ground point or any other
unpainted enclosure framework that is connected to earth ground.
Figure ii
Measure DC voltage (inverter assembly shown with far right door removed)
Inverter assembly
PV+ bus bar
PV- bus bar
F5 F6
Xantrex GT500 480 model shown