Installation manual

Electrical Specifications
975-0601-01-01 Revision B A–3
This manual is for use by qualified personnel only.
Electrical Specifications
Table A-2 provides the AC and DC specifications for the Xantrex GT500.
Table A -2 Electrical specifications
Specification
Xantrex GT500 480 and
Xantrex GT500 480 PG
Xantrex GT500 600 and
Xantrex GT500 600 PG
Nominal AC Output Voltage
(+10% to -12% default range)
480 VAC
(422 to 528 VAC)
600 VAC
(528 to 660 VAC)
Maximum Continuous AC Output Current 610 Arms 490 Arms
Nominal AC Input Frequency
(+0.5 to -0.7 Hz default range)
60 Hz
(59.3 to 60.5 Hz)
60 Hz
(59.3 to 60.5 Hz)
Line Power Factor >0.99 >0.99
Nominal Output Power 500 kW; -20 °C to 45 °C
(-4 °F to 113 °F) with de-
rating from 45 °C to 50 °C
(113 °F to 122 °F)
500 kW; -20 °C to 45 °C
(-4 °F to 113 °F) with de-
rating from 45 °C to 50 °C
(113 °F to 122 °F)
Sell Power Range 1 kW to 500 kW 1 kW to 500 kW
Peak Power Tracking Window 310 to 480 VDC 310 to 480 VDC
Maximum Open Circuit Voltage 600 VDC 600 VDC
Maximum DC Operating Current 1720 ADC 1720 ADC
Maximum Array Short Circuit Current at STC 2150 ADC 2150 ADC
Absolute Maximum Array Short Circuit Current
Under Any Conditions
2688 ADC 2688 ADC
Maximum Array Back-feed Current 0 A 0 A
AC Current Distortion < 5% THD at rated power < 5% THD at rated power
Efficiency 96.0% 96.0%
Standby and Night-time Tare Loss < 336 W < 336 W
Nominal AC Auxiliary Voltage 480 VAC single phase 600 VAC single phase
Maximum AC Auxiliary Current 11 A 8.4 A