Specifications

31
Xantrex
GT100 and GT250 Inverters
Electrical specifications
Models GT100 208 GT100 480 GT100 600 (preliminary) GT250 480 GT250 600 (preliminary)
Input (DC)
MPPT,voltagerange 300to480V 300to480V 300to480V 300to480V 300to480V
Max.opencircuitvoltage 600V 600V 600V 600V 600V
Max.DCcurrent 347A 347A 347A 867A 867A
Max.DCshortcircuitcurrent 460A 460A 460A 1214A 1214A
Max.utilitybackfeedcurrent0A 0A 0A 0A 0A
Nighttimetareloss <100W <100W <100W <100W <100W
Output (AC)
Max.continuousoutputpower 100kW 100kW 100kW 250kW 250kW
NominalACvoltage 208V 480V 600V 480V 600V
(linetoline,+10%-12%) (linetoline,+10%-12%) (linetoline,+10%-12%) (linetoline,+10%-12%) (linetoline,+10%-12%)
Nominalfrequency 60Hz 60Hz 60Hz 60Hz 60Hz
(+0.5Hz/-3.0Hz) (+0.5Hz/-3.0Hz) (+0.5Hz/-3.0Hz) (+0.5Hz/-3.0Hz) (+0.5Hz/-3.0Hz)
NominalACcurrent 278A 121A 97A 301A 241A
Max.ACcurrent 1100A 1100A TBD 1400A TBD
Powerfactor >0.99 >0.99 >0.99 >0.99 >0.99
Totalharmonicdistortion(THD)<3%atratedpower <3%atratedpower <3%atratedpower <3%atratedpower <3%atratedpower
Efficiency
Peak 96.2% 96.7% 96.7% 96.8% 96.8%
CECweighted 95.0% 96.0% 96.0% 96.0% 96.0%
General specifications
Enclosurerating NEMA3R(outdoorrating) NEMA3R(outdoorrating) NEMA3R(outdoorrating) NEMA3R(outdoorrating) NEMA3R(outdoorrating)
Enclosure Zinccoatedandpowdercoatedsteelenclosure
Weight 1361kg(3000lb) 1361kg(3000lb) 1361kg(3000lb) 2018kg(4450lb) 2018kg(4450lb)
Dimensions(HxWxD) 186.2x170.2x117.1cm 186.2x170.2x117.1cm 186.2x170.2x117.1cm 219.2x228.6x117.1cm 219.2x228.6x117.1cm
(73.3x67.0x46.1in) (73.3x67.0x46.1in) (73.3x67.0x46.1in) (86.3x90.0x46.1in) 86.3x90.0x46.1in)
(Removableairintake (Removableairintake (Removableairintake (Removableairintake (Removableairintake
reducesdepthby12in reducesdepthby12in reducesdepthby12in reducesdepthby12in reducesdepthby12in
forttingthroughdoors) forttingthroughdoors) forttingthroughdoors) forttingthroughdoors) forttingthroughdoors)
Operatingtemperaturerange -15ºCto50ºC(5ºFto122ºF)availablelowtemperatureoptionwithspaceheaters
Altitudelimit upto2012m(6600ft)withoutde-rating
Relativehumidity 0to95%non-condensing 0to95%non-condensing 0to95%non-condensing 0to95%non-condensing 0to95%non-condensing
Noise
emission <75dBA <75dBA <75dBA <75dBA <75dBA
Partnumber 1-153392-01* 1-153391-01* TBD 1-153390-01* TBD
Features and options
Coolingmethod Forcedconvectioncooling/sealeddesign
Display StandardbrightuorescentgreenVuumdisplay
Communications OptionalRS485/ModbusandRS232communicationsinterfacekit
AC/DCdisconnect Standardandintegratedwithintheinverterenclosure
Isolationtransformer Standardandintegratedwithintheinverterenclosure
Ground-faultdetection/interruption Standardandintegratedwithintheinverterenclosure
Sub-arraycombiner Optionalandintegratedwithintheinverterenclosure,100A,150Aor200Acircuits
Regulatory approvals
Safety UL1741rev.2005,CSA107.1
Interconnect IEEE1547andCSA107.1
Specificationsaresubjecttochangewithoutnotice.
*Otheroptionsavailableuponrequest.