Specifications

35
Xantrex
GT500 Inverters
Electrical specifications
Models GT500 480 (preliminary) GT500 600 (preliminary) GT500 MVX
Input (DC)
MPPT,voltagerange 310to480V 310to480V 310to480V
Max.opencircuitvoltage 600V 600V 600V
Max.DCcurrent 1700A 1700A 1700A
Max.DCshortcircuitcurrent 2200A 2200A 2200A
Max.utilitybackfeedcurrent 0A 0A 0A
Nighttimetareloss <100W <100W <100W
Output (AC)
Max.continuousoutputpower 500kW 500kW 500kW
NominalACvoltage 480V 600V 208V(fordirectconnectiontoamedium
voltageisolationtransformer)
Nominalfrequency 60Hz 60Hz 60Hz
NominalACcurrent 602A 482A 1388A
Max.ACcurrent TBD TBD 2550A
Powerfactor >0.99 >0.99 >0.99
Totalharmonicdistortion(THD) <3%atratedpower <3%atratedpower <3%atratedpower
Efficiency
Peak 97.3%(est) 97.3%(est) 98%notincludingMVtransformer
CECweighted 96.5%(est) 96.5%(est) 97%notincludingMVtransformer
General specifications
Enclosurerating NEMA3R NEMA3R NEMA3R
Enclosure Steel Steel Steel
Weight 2268kg(5000lb) 2268kg(5000lb) 1587kg(3499lb)
Dimensions(H×W×D) 224.6×379.8×126cm 224.6×379.8×126cm 224.6×228.6×126cm
(88.4×149.5×49.6in) (88.4×149.5×49.6in) (88.4×90.0×49.6in)
Operatingtemperaturerange -20ºCto45ºC(-4ºFto113ºF)lowtemperatureoptionavailabledownto-35ºC,powerderatingabove45ºC
Altitudelimit upto2012m(6600ft)withoutde-rating
Relativehumidity 0to95%non-condensing
Noiseemission <75dBA <75dBA <75dBA
Partnumber TBD TBD 820-0049-01-01*
Features and options
Coolingmethod Forcedconvectioncooling/sealeddesign
Display StandardbrightflourescentgreenVuumdisplay
Communications OptionalRS485/ModbusandRS232communicationsinterfacekit
AC/DCdisconnect Standardandintegratedwithintheinverterenclosure
Isolationtransformer Standardandintegratedwithintheinverterenclosure(480Vand600Vonly)
Ground-faultdetection/interruption Standardandintegratedwithintheinverterenclosure
Sub-arraycontainer Optionalbesidetheinverter,100A150Aor200Acircuits
Regulatory approvals
Safety UL1741rev.2005,CSA107.1
Interconnect IEEE1547andCSA107.1
Specificationsaresubjecttochangewithoutnotice.
*Otheroptionsavailableuponrequest.