Technical Data Bulletin

19-90
© 2019 Schneider Electric
All Rights Reserved
30 mm Push Buttons
Type K, SK and KX Electrical Components
schneider-electric.us
Class 9001 / Refer to Catalog 9001CT1103
Type KA Contact Blocks
Table 19.268: Standard Contact Blocks
Description Symbol Type
(Clear Cover)
Direct-Acting
KA1
(Green Cover)
KA2
(Red Cover)
Direct-Acting
KA3
(Clear Cover)
N.O. Contact Early
Closing
KA4
(Red Cover)
N.C. Contact Late
Opening
KA5
(Green Cover)
N.O. Contact Early
Closing
KA6
Table 19.269: Additional Circuit Arrangements
Description Symbol Type
Sequencing [118]
N.O. Contact of
KA4 closes before
N.O. Contact on
KA1
KA4
KA1
Order One Type
KA4 and One
Type KA1
Overlapping [118]
N.O. Contact of
KA4 closes before
N.C. Contact of
KA5 Opens
KA4
KA5
Order One
Type KA4 and
One Type KA5
The Class 9001 Type KA contact blocks are Fingersafe® contact blocks (meeting VDE
0106 Part 100). They have one screw mounting and captive (backed out) plus/minus
terminal screws. These contact blocks are double-break, direct-acting contacts. Because
of the wiping action of these contacts, they are suitable for use with programmable
controllers. All contact blocks listed below accept up to 2 #12–#24 AWG solid or
stranded wires. Recommended tightening torque for screw terminals is 7 lb-in.
Symbol
Contact Blocks with
Binder Head Screws
(not Fingersafe)
Gold Flashed Contacts
with Standard
Pressure Wire Terminals
Type [119] Quantity [120] Type [119]
KA21
25–Up
KA31
KA22
25–Up
KA32
KA23
25–Up
KA33
N.O. Early Closing
KA24
25–Up
KA34
N.C. Contact Late Opening
KA25
25–Up
KA35
Contact blocks listed below are not Fingersafe, but provide:
Terminals that accept ring tongue/fork
tongue connectors
Short single circuit contact blocks (0.75"
deep vs. 0.97" deep on the Fingersafe)
Same as old style Series G product
available prior to March, 1989.
For assembled operators, use form Y238
(add to catalog number as suffix, for
example: 9001KRU1H13Y238)
Table 19.270: Contact blocks (not Fingersafe)
Symbol Type [119] Symbol Type [119]
KA1G
N.O. Contact Early Closing
KA4G
KA2G
N.C. Contact Late Opening
KA5G
KA3G
N.O. Contact Early Closing
KA6G
Table 19.271: Contact blocks with Quick-Connect terminals (not Fingersafe)
Symbol Type [119]
KA12
KA13
Table 19.272: Maximum Current Ratings for Control Circuit Contacts—Types KA1–KA6, KA21–KA25, KA31–KA35, KA1G–KA6G
Volts
AC
Volts
DC
Inductive (NEMA / UL Type A600) 35% Power Factor
Resistive 75%
Power Factor
Make, Break
and
Continuous
Amperes
Inductive and Resistive
(NEMA Q600)
Make Break
Continuous
Carrying
Amperes
Make and Break
Continuous
Carrying
Capacity
Amperes
VA
Amperes
VA KA1
KA2
KA3
KA4
KA5
KA6
120 60
7200
6.0
720 10 10
125 0.55 0.55
2.5240 30 3.0 250 0.27 0.27
480 15 1.5 600 0.10 0.10
600 12 1.2
19
PUSH BUTTONS AND OPERATOR
INTERFACE
[118] For push buttons or two-position selector switches only. For sequencing or overlapping contacts on other operators, refer to catalog 9001CT0001.
[119] When ordering, add prefix 9001 to the catalog number.