Characteristics (continued)
Characteristics of contact or combined contact and signalling functions (continued) (see page 92)
Electrical characteristics (continued)
Rated operational characteristics
Conforming to EN/IEC 60947-5-1
a.c. supply:
utilisation category AC-15
Standard single and double blocks with screw
clamp or spring terminals
A600: Ue = 600 V and le = 1.2 A or
Ue = 240 V and le = 3 A or
Ue = 120 V and le = 6 A
Blocks for plug-in connector:
A300: Ue = 120 V and le = 6 A or
Ue = 240 V and le = 3 A
Standard blocks for printed circuit board
connection:
B300: Ue = 120 V and le = 3 A or
Ue = 240 V and le = 1.5 A
Special contact blocks:
ZBE 201: A300: Ue = 240 V and le = 3 A or
Ue = 120 V and le = 6 A (with insulation
voltage Ui = 500 V)
ZBE 202: A600: Ue = 600 V and le = 1.2 A or
Ue = 240 V and le = 3 A or Ue = 120 V and le = 6 A
Contact blocks for high power switching:
ZBE 50p: A300: Ue = 240 V and le = 3 A or
Ue = 120 V and le = 6 A
v
v
v
d.c.supply:
utilisation category DC-13
Standard single and double blocks with screw
clamp or spring terminals
Q600: Ue = 600 V and le = 0.1 A or
Ue = 250 V and le = 0.27 A or
Ue = 125 V and le = 0.55 A
Joystick controllers XD5 PA/ZD5 PA:
R300: Ue = 125 V and le = 0.22 A or
Ue = 250 V and le = 0.1 A
Blocks for plug-in connector:
R300: Ue = 125 V and le = 0.22 A or
Ue = 250 V and le = 0.1 A
Standard blocks for printed circuit board
connection:
R300: Ue = 125 V and le = 0.22 A or
Ue = 250 V and le = 0.1 A
Special contact blocks:
ZBE 201: Q300; Ue = 125 V and le = 0.55 A or
Ue = 250 V and le = 0.27 A
ZBE 202: Q600; Ue = 600 V and le = 0.1 A or
Ue = 250 V and le = 0.27 A or Ue = 125 V and
le = 0.55 A
Contact blocks for high power switching:
ZBE 50p: P300: Ue = 125 V and le = 1.1 A or
Ue = 250 V and le = 0.55 A
v
v
v
Characteristics of
special contact blocks
Low power switching VA
A
V
P max: 12
I max: 0.1
U max: 24
High power switching
conforming toEN/IEC 60947-5-1
100 000 operating cycles
Load factor: 0.5
Operating rate: 900 cycles/hour
VA
A
V
P max: 240
I max: 10
U: 24 c
Electrical durability
Conforming to EN/IEC 60947-5-1 appendix C
Operating rate 3600 operating cycles/hour
Load factor: 0.5
a.c. supply
for 1 million operating cycles
utilisation category AC-15
Standard single blocks with screw clamp terminals
or spring terminals:
V
A
24
4
120
3
230
2
Standard double blocks with screw clamp terminals
and blocks for plug-in connector:
V
A
24
3
120
1.5
230
1
d.c. supply
for 1 million operating cycles
utilisation category DC-13
Standard single blocks with screw clamp terminals
or spring terminals:
V
A
24
0.5
110
0.2
Standard double blocks with screw clamp
terminals and blocks for plug-in connector:
V
A
24
0.4
110
0.15
Electrical reliability
Failure rate
Conforming to EN/IEC 60947-5-4
In clean environment Standard blocks:
at 17 V and 5 mA, l < 10
-8
at 5 V and 1 mA, l < 10
-6
Special blocks with gold ashed contacts, for low
power switching:
at 5 V and 1 mA, l < 10
-7
-
-
-
In dusty environment Special blocks with gold ashed contacts and dust
protection for low power switching only:
at 5 V and 1 mA, l < 10
-7
-
General:
References:
Dimensions:
General:
References:
Dimensions:
General:
References:
Dimensions:
General:
References:
Dimensions:
Control and signalling units Ø 22
Harmony
®
XB5 plastic
Pushbuttons, switches and pilot lights
1
2
3
4
5
6
7
8
9
10