Manual

PROFIBUS Network Interface
EIO0000000046 04/2013 23
Fieldbus Connection
Description
The splitter box can either be in the middle of the chain connection or at line end.
The fieldbus is connected via 5-pin M12 connectors (B-coding).
Pin Assignment
The following diagram shows a front view of the bus connectors (B-coding)
NOTE: It is preferable to connect the shielding to the connector housing. If this is not
possible, the connection can also be made using pin 5. These two possibilities can
also be combined.
Pin Signal Description
1 VP Line terminator polarization voltage
2 A - RxD/TxD-N Receive/transmit data - negative (green)
3 DGND Discrete earth
4 B - RxD/TxD-P Receive/transmit data - positive (red)
5 Shielding Shielding or earthing
Connector
housing
Shielding Shielding or earthing