Manual

Data Access to OsiSense® XG Stations
32
EIO0000000046 04/2013
Data Buffer Structure
The following table describes the Output Data Buffer structure of the Splitter Box
XGS Z33PDP:
NOTE: Communication errors can result if the maximum number of words is
exceeded.
Register
(16 Bits)
Description
1st NA
2nd Bit 0 = Read command trigger bit
3rd Bit 0 = Write command trigger bit
4th RFID station slave address (1 to 15)
5th Start address of the Read/Write command
6th Quantity of registers to Read/Write (1 to 49)
7th Quantity of bytes to Read/Write (2 x qty of registers)
8th Data 1 Used only for write
command
9th Data 2
10th Data 3
... ...
... Data n
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed the maximum number of words to read or write.
Communication errors can result if the maximum number of words is exceeded.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.