Software Installation
42
EIO0000000046 04/2013
Second Phase: PL7 Pro/Unity
The second phase is performed by PL7 Pro or Unity. Once the ASCII file is selected,
the master initializes the network devices and gives them the start-up command.
Proceed as follows:
Step Action
1 In the TSX PBY100 card configuration screen, select the ASCII configuration
file (.cnf) generated by SyCon by clicking on the Load CNF button.
The "PROFIBUS-DP slave configuration" area then shows all the configured
slaves. In the following illustration, the master is at address 2 and the
OsiSense
®
XG PROFIBUS Splitter Box is at address 10.
By clicking a line corresponding to a slave, you can see the address and length
of the modules declared using SyCon.
The length of the PLC’s diagnostic buffer is set to 32 bytes by default. However,
it may be set to up to 244 bytes (maximum length) to prevent any overflow.
2 Validate the config by clicking on Validate in the Edit menu.