Diagnostics
48
EIO0000000046 04/2013
Diagnostic LEDs
Description
6 LEDs allow you to diagnose the Splitter Box communication status:
(1)
Specific errors indicated by the LED 4 FIELDBUS DIAG
No. DEL Status Description
1 ONLINE Off PROFIBUS-DP bus: Splitter Box off-line
Green PROFIBUS-DP bus: Splitter Box on-line (exchanges are possible)
2 OFFLINE Off PROFIBUS-DP bus: Splitter Box on-line
Red PROFIBUS-DP bus: Splitter Box off-line (exchanges are impossible)
3 NOT USE Off -
4 FIELDBUS DIAG Off Initialization achieved
Flashing red (1 or
2Hz)
Configuration error
(1)
Flashing red
(4 Hz)
Error when resetting the Splitter Box on PROFIBUS-DP
(1)
5 MODBUS Off No power
Flashing green No Modbus communications
Green Modbus communications OK
Red
Loss of communications with at least one Modbus slave
(2)
Exception code coming from a command or a transaction
6 GATEWAY Off No power
Flashing
(red/green)
Configuration absent / not valid (Use ABC-LUFP Config Tool to load a
valid configuration)
Green Splitter Box currently being initialized and configured
Flashing green Splitter Box is in running order, configuration OK