Software setup
24
English
W916556680111
3 During the first connection, users are asked to change the password of the
Device. (Due to Cyber-security Califonia Law, all the devices with IP
address should be protected through password).
4 Configure the parameters for function 1) Network/IP Settings.
Initial configuration of parameters 2 and 4:
It is possible to start the configuration procedure again from the beginning at any
time by reinitializing the splitter box (turning off the power).
The diagnostics LED (red) is on during configuration.
5 Reconfigure the computer IP address with an address that is compatible
with the splitter box one.
(Example: Splitter box = 192.168.0.220 -> PC = 192.168.0.1).
NOTE: Except the "Modbus Serial Broadcasts" parameter, functions 2) and 4)
correspond to parameters that must not be modified. In case of error, revert to
the initial configuration
2) Serial & Mode Settings:
Protocol...................... Modbus/RTU, Slave(s) attached
Serial interface ............. 57600,8,E,1,RS485
4) Advanced Modbus Protocol settings:
Slave addr/unit Id Source..... Modbus/TCP header
Modbus Serial Broadcasts...... Disabled (Id=0 auto-mapped to 1)
MB/TCP Exception codes ....... Yes (return 00AH and 00BH)
Char, Message Timeout......... 00050msec, 05000msec
Telemecanique - Modbus Bridge (XGSZ33ETH)
MAC address 0080A36A1A62
Software version V3.4.16.8A3 (210427) UDS1100
Password :