Manual

Table Of Contents
Software setup
26
English
W916556680111
4 Open a Telnet connection on port 9999, and press the Enter key within three
seconds to switch to Setup mode. If you wait longer than three seconds, the
unit will restart (begin the procedure again).
The IP address of the box is displayed (here: 192.168.0.220). To change it,
follow the 2.2.1 procedure.
Syntax
telnet "IP ADDRESS" 9999
Example
telnet 192.168.0.10 9999
Result The following window appears
Telemecanique - Modbus Bridge (XGSZ33ETH)
MAC address 0080A36A1A62
Software version V3.4.16.8A3 (210427) UDS1100
Password :----
Press Enter for Setup Mode
Model: Device Server Plus+! (firmware Code:UA)
Modbus/TCP to RTU Bridge Setup
1) Network/IP Settings:
IP Address ................. 192.1968.0.220
Default Gateway ............ --- not set ---
Netmask .................... --- not set ---
Telnet config passqord set
2) Serial & Mode Settings:
Protocol ................... Modbus/RTU, slave(s) attached
Serial Interface ........... 57600,8,E,1,RS485
3) Model Control Settings:
Modem control not available with RS422/RS485
4) Advanced Modbus Protocol settings:
Slave Addr/Unit Id Source .. Modbus/TCP header
Modbus Serial Broadcasts ... Disabled (Id=0 auto-mapped to 1)
MB/TCP Exception Codes ..... Yes (return 00AH and 00BH)
Char, Message Timeout ...... 00050msec, 05000msec
7) Security Settings:
SNMP ....................... Disabled
Telnet Setup ............... Enabled
TFTP Download ............. Disabled
Port 77FEh ................. Enabled
Web Server ................. Disabled
Enhanced Password .......... Enabled
D) efault settings, S)ave, Q)uit without save
Select Command or parameter set (1..7) to change: