Data Sheet

Complementary
Synchronisation time between inputs < 0.5 s
Power consumption in W <= 3 W DC
Input protection type Internal, electronic
Time delay range 0.15...3 s
1.5...30 s
[Uc] control circuit voltage 24 V DC
Breaking capacity B300 : 3600 VA, AC-15 (inrush)
B300 : 360 VA, AC-15 (holding)
Breaking capacity 1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
Output thermal current 6 A for instantaneous and time delay outputs
[Ith] conventional free air thermal current 12 A
Associated fuse rating 6 A fuse type gG for instantaneous and time delay outputs conforming-
to EN/IEC 60947-5-1, DIN VDE 0660 part 200
Minimum output current 10 mA for relay output
Minimum output voltage 17 V for relay output
Response time on input open <= 200 ms
[Ui] rated insulation voltage 300 V (degree of pollution: 2) conforming to DIN VDE 0110 part 1
300 V (degree of pollution: 2) conforming to IEC 60947-5-1
[Uimp] rated impulse withstand voltage 4 kV overvoltage category III conforming to IEC 60947-5-1
4 kV overvoltage category III conforming to DIN VDE 0110 part 1
Local signalling 3 LEDs
Mounting support 35 mm symmetrical DIN rail
Product weight 0.28 kg
Environment
Standards EN 1088/ISO 14119
EN/IEC 60204-1
EN/IEC 60947-5-1
EN/ISO 13850
Product certifications BG
CSA
UL
IP degree of protection IP40 conforming to EN/IEC 60529
IP20 conforming to EN/IEC 60529
Ambient air temperature for operation -25...55 °C
Ambient air temperature for storage -25...75 °C
Contractual warranty
Warranty period 18 months
Product Life Status : Commercialised
2