Configuration
3–6 975-0400-01-01 Revision H
This manual is for use by qualified personnel only.
Table 3 - 2 Battery Menu Values
Setting Values Default Description


Activate/Stop Activate Enables or disables Battery
Equalization. If the Battery
Type is set to GEL or AGM,
this setting is disabled.


0–365 d(ays) 0 d Sets a reminder that notifies
you when the battery needs
equalizing. If set to 0, the
reminder is disabled.


1–12 1 Selects the battery bank
connected to the solar
charge controller. This is
important for networked
installations, where multiple
devices must coordinate their
activity around common DC
connections.


1 2V, 2 4 V, 36 V,
48V, 60V
n/a Selects your battery voltage.
Select the nominal voltage
level that matches your
system’s battery voltage.


Flooded, GEL,
AGM, Custom
Floode
d
Selects your battery type.
Selecting Custom allows you
to adjust the Equalize, Bulk,
Absorption, and Float Voltage
settings. Battery temperature
compensation can also be
adjusted on the Custom
Battery menu. The Custom
option is available only when
advanced menus are
displayed.


n/a n/a Press Enter to display the
Custom Battery menu and
configure a custom battery
type. See “Setting a Custom
Battery Type” on page 3–8.

 
50–2000Ah
6.0–60.0A
440Ah
60.0A
Line 1: Sets the amp-hour
capacity of your battery
bank.
Line 2: Sets the charging
current limit.