Schneider Electric XW-MPPT-60 User Manual

Monitoring Charge Controller Operation
975-0400-01-01 Revision H 4–9
This manual is for use by qualified personnel only.
Viewing Active Faults and Warnings
You can view active faults and warnings from the Faults and Warnings Menu.
Warning messages indicate a problem that could affect normal operation.
“Warning Active” appears on the LCD to notify you of the warning condition.
Normal operation continues until the warning condition:
clears and normal operation continues
escalates to a fault condition.
Fault messages indicate a fault condition. When a fault occurs, the solar charge
controller:
displays “Fault Active” on the LCD
disables the MPPT and charging functions
opens the relay that connects its power circuits to the battery bank.
The only fault that does not disable normal solar charge controller operation is
the Auxiliary Output Overload Fault. The Auxiliary Output Overload Fault only
disables the auxiliary output. Other solar charge controller functions continue
operating. The Ground Fault disables the auxiliary output as well as normal solar
charge controller operation.
Most warnings and faults clear automatically once the condition that caused
them goes away. The only exceptions are the Auxiliary Output Overload Fault
and the Ground Fault. The Auxiliary Output Overload Fault must be cleared
manually. The Ground Fault requires you to correct the ground fault and restart
the system. For more information, see Troubleshooting.
To view the complete list of active faults and warnings:
1. Press Enter on the Active Faults and Warning Menu screen.
2. Press the down button to view additional fault or warning messages.
If there are no active faults and warnings, no messages are displayed after
you press Enter from the Active Faults and Warnings screen.
To manually clear a fault:
1. Identify the active fault from the Active Faults and Warning Menu.
The two faults you can manually clear are “Batt Under Volt” (except when the
battery voltage has fallen below 10 V) and “Aux Output Ovld.” and See Table
4-6 for descriptions of these faults.
2. Press Exit to return to the Active Faults and Warnings Menu, then press the
down arrow to view the Clear Fault screen.
“Batt Under Volt” is displayed first.
3. Press Enter to view the cursor.
Note
: The Faults and Warnings menu is visible only when the solar charge
controller has one or more active faults or warnings.