Schneider Electric Owner's Guide
Configuration
2–6 975-0560-01-01 G
A safety notice when selecting battery charge settings when the Conext MPPT 80
600 is part of a power system with a Conext XW+ Inverter/Charger is shown
below.
Advanced Settings >
Charger Settings
Default Batt
Temp
Cold
Warm
Hot
Warm Sets the default battery
temperature for compensation
when a BTS is not connected.
Cold is suitable for
temperatures around 10°C
(50°F), Warm for 25°C (77°F),
and Hot for 40°C (104°F). This
screen appears only when a
BTS is not connected.
Setup >
Meters
Batt Temp -40–65 C n/a Shows the battery temperature
(in Celsius) detected by the
BTS. This screen appears only
when a BTS is connected.
Advanced Settings >
Charger Settings
Charge Cycle 3Stage
2StgNoFloat
3Stage Sets the charging cycle: three-
stage (bulk, absorption, float) or
two-stage (bulk, absorption, no
float).
Table 2-1 Battery configuration settings
SCP Device Menu
Item Setting Values Default Description
NOTICE
DAMAGE FROM HAVING DIFFERENT CHARGER SETTINGS
Make sure that all Conext MPPT 80 600 units and all Conext XW+ Inverter/
Charger units in a power system setup has the same Charger Settings. For
example, if one Conext MPPT 80 600 unit has a Battery Type of Flooded, all
Conext MPPT 80 600 units including all Conext XW+ Inverter/Charger units
must have the same Battery Type. See NOTE below.
Failure to follow these instructions may damage the battery/batteries.
Note
: If Cascading is Enabled in SCP, the charger settings will cascade to
other Conext MPPT 80 600 devices with the same DC Associations. However
they will not cascade to other device types such as Conext XW+, Conext SW, or
Conext Battery Monitor even if they have the same DC associations. Make sure
that the charger settings are configured correctly on the other device types.