Schneider Electric Owner's Guide

Configuration
2–8 975-0560-01-01 G
See “Default Battery Charging Settings” on page A–5 for default settings for
standard battery types.
Eqlz Voltage 24V: 27.0–32.0V
48V: 54.0–64.0V
32.0V
64.0V
Sets the equalization voltage (consult your battery
manufacturer for equalization voltage setting).
This screen is hidden if Eqlz Support is
disabled.
Bulk Voltage 24V: 20.0–32.0V
48V: 40.0–64.0V
28.8V
57.6V
Sets the bulk voltage for a custom battery.
Absorb Voltage 24V: 20.0–32.0V
48V: 40.0–64.0V
28.8V
57.6V
Sets the absorption voltage for a custom battery.
Float Voltage 24V: 20.0–32.0V
48V: 40.0–64.0V
27.0V
54.0V
Sets the float voltage for a custom battery.
BattTempComp 24V: -90–0mV/degC
48V: -180–0mV/degC
-54mV
-108mV/C
Sets the battery temperature compensation for a
custom battery. This setting is the reference that
the BTS uses to adjust the charging voltage when
the temperature falls above or below 25°C. See
“Battery Temperature Compensation” on page 2–9.
Table 2-2 Custom battery settings
Setting Values Default Description
NOTE
EQUIPMENT DAMAGE
Check the battery specifications carefully before changing the settings for
bulk, absorption, float and equalization charging. The charge controller is
incapable of determining battery type and cannot warn against or disallow
incorrect settings. Incorrect settings may damage the battery or shorten
battery life.
Failure to follow these instructions can damage equipment.