Schneider Electric Owner's Guide
Configuration
2–12 975-0560-01-01 G
Trig Src Configurable:
LowBattV
HighBattV
LowArrayV
HighArrayV
LowBattTemp
HighBattTemp
HighHsTemp
Not configurable:
Fault
GroundFlt1
GroundFlt2
InputOVFlt
InputOVErr
InputOVWrn
OutputOVErr
OutputOVWrn
OutputOCErr
BattOTErr
BattOTWrn
BattUTWrn
HsOTErr
HsOTWrn
AmbOTErr
AmbOTWrn
CapOTErr
FanErr
FanFlt
OutputUVErr
OutputUVWrn
InputOCErr
OutputOCFlt
NetPSFlt
LowBattV Sets the desired condition to activate the auxiliary
output. Changing Trig Src while the auxiliary output is
already in the triggered state resets the auxiliary output.
If Trig Src is set to LowBattV or HighBattV, then
changing battery voltage (see Table 2-1 on page 2–4)
will reset Trigger Level and Clear Level to their
default values.
For a description of the non-configurable faults, errors,
and warnings that you can set for Trig Src, see Table
3-4, “Fault messages” on page 3–6, Table 3-5, “Error
messages” on page 3–7, and Table 3-6, “Warning
messages” on page 3–9.
Trigger
Level
Depends on Trigger Source
(see Table 2-5)
Sets the battery or array voltage to activate the auxiliary
output. If the selected trigger source is HighBattTemp,
LowBattTemp, or HighHsTemp, this screen displays
Trigger Temperature Level in degrees Celsius.
Changing Trigger Level while the auxiliary output is
already in the triggered state resets the auxiliary output.
This setting is hidden if the trigger source is set to an
error, warning, or fault.
Table 2-4 Aux menu settings
Setting Values Default Description
975-0560-01-01(XW-MPPT80-600_Ops).book Page 12 Wednesday, November 22, 2017 5:52 PM