Schneider Electric Owner's Guide
Configuration
2–16 975-0560-01-01 G
Configuring Device Settings
From various menus, you can change the operating mode of the charge
controller and view the charge controller’s device number. These activities might
be necessary when performing service or diagnostics as well as when adding
another Xanbus-enabled device to the system.
NOTICE
EQUIPMENT DAMAGE
Any configuration (change in settings) made when the Conext MPPT 80 600 is
in Operating mode will not be saved unless the MPPT is put in Standby and
then back to Operating mode. It is recommended to put the MPPT in Standby
mode prior to changing basic or advanced settings. Then return to Operating
mode for the settings to take effect.
Failure to follow these instructions can damage equipment.
Table 2-6 Device settings
SCP Menu Item Setting Values Default Description
Setup Mode Operating
Standby
Operating Operating is the normal mode
for the charge controller.
Standby disables the charge
controller so that it cannot
charge. The charge controller
still draws some power from
the battery to operate.
Advanced Settings >
Multi Unit Config
Dev Number 00 to 31 00 Displays the device number
for the charge controller. This
number is set when the
charge controller is
commissioned and uniquely
identifies devices of the same
type (charge controllers,
inverter/chargers, control
panels, and so on) in a
networked installation.
Select Device >
System Settings >
View Device Info
F/W Rev. 1.00.00 BN 5 N/A N/A Firmware version and
firmware build number.
975-0560-01-01(XW-MPPT80-600_Ops).book Page 16 Wednesday, November 22, 2017 5:52 PM