Schneider Electric Owner's Guide

Operation
3–8 975-0560-01-01 G
BattOTErr
(Battery over
temperature error)
F4 Battery temperature has risen above 60°C (140°F) for 30 seconds.
The error clears itself when the battery temperature falls below
55°C (131°F) for 30 seconds.
AmbOTErr
(Ambient over
temperature error)
F5 Ambient temperature inside the charge controller has risen above
80°C (176°F) for 5 seconds. The error clears itself when the
ambient temperature falls below 65°C (149° F) for 30 seconds.
InputOVErr
(Input over voltage
error)
F9 Input voltage has exceeded the input over voltage shut off value,
which is dependent upon temperature measured on the heatsink
(Vin High Threshold in Figure 3-2 on page 3–11). The error clears
itself when the input voltage falls below the input over voltage
restart value (Vin Restart Threshold in Figure 3-2 on page 3–11).
OutputUVImmErr
(Output under voltage
immediate error)
F10 Output voltage has fallen below 15.8 VDC. The error clears itself
when the voltage rises above 19.0 VDC for 1 second.
OutputUVErr
(Output under voltage
error)
F11 24 V System: Output voltage has fallen below 18.0 VDC. The error
clears itself when the voltage rises above 19.0 VDC for 1 second.
48 V System: Output voltage has fallen below 36.0 VDC. The error
clears itself when the voltage rises above 38.0 VDC for 1 second.
AuxPSErr
Auxiliary power supply
error
F26 Auxiliary power supply is not within its expected operating range.
The error clears itself after 1 second and the auxiliary power
supply will attempt to restart.
HsOTErr
(Heat sink over
temperature error)
F55 Heat sink temperature has risen above 90°C (194°F) for
5 seconds. The error clears itself when the heat sink temperature
falls below 80°C (176°F) for 30 seconds.
SetupErr F69 Multiple charge controllers connected to the Xanbus network have
the same device number. The error will clear when the operator
changes the device numbers of the duplicate charge controllers.
The device number can be changed in the Multi Unit Config
screen of the SCP.
OutputOVErr
(Output over voltage
error)
F70 24 V System: Output voltage has risen above 34.5 VDC for
1 second. The error clears itself when the voltage falls below 32.0
VDC for 1 second.
48 V System: Output voltage has risen above 69.0 VDC for
1 second. The error clears itself when the voltage falls below 64.0
VDC for 1 second.
Table 3-5 Error messages
Display Text
(Description) Error ID Definition
975-0560-01-01(XW-MPPT80-600_Ops).book Page 8 Wednesday, November 22, 2017 5:52 PM