Schneider Electric Owner's Guide

Operation
3–16 975-0560-01-01 G
Remote Power Off (RPO)
It is possible to immediately stop the operation of the SCP charge controller by
adding a remote power off (RPO) switch via the Conext XW+ Inverter/Charger’s
AUX port.
An RPO switch turns off the internal network power supply of the charge
controller. When activated, Xanbus devices such as the Conext XW+ Inverter/
Charger and the Conext MPPT 80 600 will stop all operation including solar
charging effectively transitioning the power system into a standby mode.
For information on the different modes, see “Mode” on page 2–16.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not attempt to service, maintain, and troubleshoot the Conext MPPT 80
600 after activating an RPO switch.
Disconnect PV conductors before servicing. PV conductors are to be
treated as Hazardous Live and must be disconnected.
Normally GROUNDED conductors may be UNGROUNDED and
ENERGIZED when a GROUND FAULT is indicated on the front panel. Must
be serviced by qualified personnel.
Failure to follow these instructions will result in death or serious injury.