XW Power Distribution Panel
XW Series Power Distribution | 3
XW PDP with AC Breakers XW PDP without AC Breakers
Part number 865-1015-01 865-1014-01
Standards UL UL / IEC
AC Distribution
Included breakers
Three 60 A, 120/240 Vac, two-pole, Square D
QOU260 AC breakers for AC input, bypass and
AC load (factory-installed)
Breakers not included. Refer to compatible
breaker accessories.
Mounting DIN rail (35 mm) DIN rail (35 mm)
Breaker expansion positions Six expansion positions
1
Nine 2-pole expansions (QOU breakers)
AC wiring
Factory installed and labeled Arctic Ultraflex
Blue
TM
wiring, including five #6 AWG AC cables
for AC connections: L1, L2, Neutral
AC wiring not included
DC Distribution
Included breakers One GJ 250A 160 Vdc DC, 3/8” stud breaker installed
Mounting Panel mounted
Breaker expansion positions
Two expansion positions for battery 250A DC breakers
Eight expansion positions for charge controller DC breakers
DC wiring One pair of Arctic Ultraflex Blue
TM
#4/0 AWG battery cables
General Specifications
Wiring connections Termination lugs for ground, AC neutral and DC bus bar for battery connection
Enclosure
Indoor rated, field-reversible panel door. A wall mount bracket is included, as well as an XW Conduit
box for wiring to the XW terminals.
Product dimensions (H x W x D) 76.1 x 40.6 x 21.0 cm (30.0 × 16.0 × 8.3 in)
Shipping dimensions (H x W x D) 122.0 x 53.3 x 34.3 cm (48.0 × 21.0 × 13.5 in)
Shipping weight 30.5 kg (67.2 lb)
The XW Power Distribution Panel (PDP) provides an easy to install DC
and AC power distribution cabinet compatible with the Conext XW series
inverters. The PDP can be used for managing power distribution for
up to three XW inverters, MPPT Charge Controllers, the battery, and a
generator.
The PDP is designed for easy installation and flexibility:
Includes a main 250 A DC breaker for the battery
Available with or without AC breakers for AC input, Bypass, and AC Out
(load)
Breaker expansion positions on DC side for solar charge controllers
and additional battery disconnects/breakers and AC side for additional
inverters, generator or AC coupled PV inverter
Compatible with up to three XW inverters
Provision for mounting surge arresters e.g. Square D SDSA1175, Square D SDSA3650
Extremely flexible Arctic Ultraflex Blue
TM
wiring for direct connection to the XW inverter as described in the
specifications
Split phase, single phase, and three phase applications
Mount on either side of the XW inverter, multiple conduit knockouts and a field reversable door
Mounts flush beside Conext 600V MPPT Charge Controllers. Includes mounting provisions for two MPPT 60 150
Charge Controllers on the side
Saves installation time with factory installed, ready to connect wiring
Includes a Conduit Box and mounting plate for seamless integration with XW inverters
1
When using the 60A, 120/240 VAC breaker kit for a two-inverter system, the bypass switch with interlock