Conext Automatic Generator Start Installation

Generator Starting Types
975-0307-01-01 B–3
Two Wire
The two-wire type is suitable for generators that are fully automatic. This
merely requires two wires to be connected together for the generator to
start and run. Separating the wires stops the generator.
Some generators use a momentary two-wire connection for starting and
stopping.
Identification
Generators of this type are usually operated with a simple toggle switch
or key that turns to on, then off to shut the generator off.
Connection
For this type of generator, the two wires are connected to the normally
open and common contacts of Relay 1 (wires 14 and 16). When the
Xantrex XW AGS receives a command to start the generator, it closes the
contacts inside Relay 1, allowing the generator to start. The contacts
remain closed for the duration of the generator run and open when the
Xantrex XW AGS needs the generator to stop.