Connecting the Generator
To connect the Xantrex XW AGS to a generator, identify the start wiring
configuration of the generator to be used. Generators must be auto-start
capable, and generators equipped with remote operation connections
are ideal.
If the generator is equipped for remote operation, examine the wiring of
the remote cable and connector (or read the generator’s documentation,
if available) and identify the following wires:
•Ground
•Start
•Stop
Generator run signal, also known as the Hour Meter or Switched B+
(battery positive)
Wiring
Requirements
Either #16 or #18 AWG wire is required to connect to the wiring harness.
How many of these wires you connect and in which combination
depends on your generator type.
CAUTION: Equipment Damage
Before connecting the Xantrex XW AGS to your generator, read the
Generator Type descriptions in this section and consult your generator
manufacturer to ensure that Gen Type settings and connections are
compatible with your generator. Damage to the generator can result from
selecting an incorrect Gen Type and following the connection diagram
for an incorrect Gen Type when connecting the Xantrex XW AGS to the
generator. Xantrex Xantrex assumes no responsibility or liability for loss
or damage that might arise out of the use of this information.