Conext Automatic Generator Start Installation

Installation
2–10 975-0307-01-01
Type 1
Type 1 is a three-wire GlowStop configuration recommended for “three-
wire” generators with glow plugs that need to be operated before a start
is attempted.
Figure 2-7 Type 1 Connection Diagram
Table 2-5 Type 1 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
GlowStop
Relay 3 mode
No function
Gen Run signal hold
time
0.5 s
Preheat time
20 s
Preheat to crank delay
1 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
0 s
Start tries
3
18
17
16
14
13
12
Relay 1
Relay 2
5A fuse
5A fuse
GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
PREHEAT
START
XW AGS Harness Wires Generator Wires
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
PREHEAT
START